Troubleshooting
Samsung Electronics
22
6-2-5 When the Outdoor Unit Does Not Operate. (Initial Diagnosis)
1. Checklist :
1) Is input voltage normal?
2) Is the set temperature of the remote control higher than room temperature in COOL mode?
3) Is the set temperature of the remote control lower than room temperature in HEAT mode?
4) Is the POWER IN connector (CN71) linked correctly?
5) Is the outdoor unit properly connected with the TERMINAL BLOCK connector(N(1), 1, 2, 3)?
2. Troubleshooting procedure
After unplugging out the power cord should be
reconnected within 5 seconds.
Does the OPERATION lamp blink
Yes
No
Yes
No
No
No
Yes
Yes
Outdoor unit is
out of order.
Power relay is
out of order
Power relay should be
replaced.
PCB should be
checked.
Micom is
out of order.
Sensor Should be
replaced
Room temperature sensor is
out of order
Check as in the procedure "No Power"
Is the room sensor normal resistor?
10°C
20°C
30°C
17.96k
Ω
12.09k
Ω
8.3k
Ω
Does the timer lamp blink during operation ?
Is the power relay RY71 operated by adjusting the
room temperature?
Is rating voltage ±10% range applied relay between
Terminal block No. N(1) and No. 1
Test rod location
Normal
+
-
Condition
Voltage
IC4 Pin No.38
GND
RY71 ON
DC 4.8V
#
!
!
@
#
@
No
Yes
DB98_16999A(2)_1 04/3/12 10:27 AM Page 22
Summary of Contents for SC07AS2
Page 4: ...3 Samsung Electronics 1 2 Pressure Graph SC07AS2 SC07AS2A SC09AS2 SC12AS4...
Page 26: ...MEMO 25 Samsung Electronics...
Page 31: ...Samsung Electronics 30 7 3 Ass y Control In Indoor Unit SC07AS2 SC07AS2A SC09AS2 DB93 02524B...
Page 33: ...Samsung Electronics 32 Exploded Views and Parts List SC12AS4 DB93 02539B...
Page 36: ...35 Samsung Electronics 9 PCB Diagram 9 1 ASS Y MAIN PCB 7K 9K 12K DB93 02447B TOP...
Page 37: ...Samsung Electronics 36 PCB Diagram BOTTOM...
Page 44: ...MEMO 43 Samsung Electronics...
Page 45: ...MEMO Samsung Electronics 44...