1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power
supply in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Before installing the indoor unit, assign an option to the indoor unit according
to the air conditioning system plan.
- The default setting of an indoor unit installation option is “02000-100000-200000-300000”.
- Individual control of a remote controller(SEG20) is The function that controls an indoor unit individually when there is
more than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
- When entering Address option, connect remote controller receiver.
Setting an indoor unit installation option (suitable for the condition of each installation location)
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Central control
Indication and Details
Indication Details Indication
Details
Indication
Details
Indication Details
Indication
Details Indication Details
0
2
0
0
0
No use
0
1
Use
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
Master / Slave
Indication and Details
Indication Details Indication
Details
Indication
Details
Indication Details
Indication
Details Indication Details
1
0
0
0
0
0
Master
1
Slave
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Explanation
PAGE
External control
External control output
Buzzer
Indication and Details
Indication Details Indication
Details
Indication
Details
Indication Details Indication
Details
Indication Details
2
0
No use
0
Thermo ON
0
0
Use
0
1
On/Off control
1
No Use
1
Operation ON
2
Off control
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
Indication and Details
Indication Details Indication
Details
Indication
Details
Indication Details
Indication
Details Indication Details
3
0
0
0
0
0
▶
If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as "indoor 1".
•When“A”~”F”isenteredtoSEG4~6,theindoorunitMAINADDRESSisnotchanged.
•IfyousettheSEG3as0,theindoorunitwillmaintainthepreviousMAINADDRESSevenifyouinputtheoptionvalueofSEG4~6.
•IfyousettheSEG9as0,theindoorunitwillmaintainpreviousRMCADDRESSevenifyouinputtheoptionvalueofSEG11~12.
5. The MAIN address is for commnication between the indoor unit and the outdoor unit. Therefore, you must set it to
operate the air conditioner properly.
Indoor Unit
1(L)
2(N)
F2
F1
Setting an indoor unit address and installation option