Connecting the Unit (Continued)
Setup the Centralized Group Control (1:1 group, 16 Groups Control)
If the 00 switch of the centralized controller is set to ON position,
16 ventilators which are set as 0 of their RMC ADDRESS are operating
simultaneously. Up to 256 of ventilators can be controlled at once.
To centralized group control, set all of the RMC ADDRESS of all ventilators
to be controlled as the same number which is controlled by the centralized
controller.
Setup the Centralized Control (Continued)
Master Ventilator
Transmitter 0
Centralized Controller
Transmitter F
Ventilator
Ventilator
Ventilator
Ventilator
MAIN:0
RMC:0
MAIN:1
RMC:0
MAIN:2
RMC:0
MAIN:3
RMC:0
Master Ventilator
MAIN:0
RMC:F
Ventilator
Ventilator
Ventilator
Ventilator
MAIN:1
RMC:F
MAIN:2
RMC:F
MAIN:3
RMC:F
MAIN:F
RMC:0
MAIN:F
RMC:F