Enclosure unit partition design
Partition design guide
When using the product with an enclosure unit, add partitions between the inlet and outlet to keep air paths separated.
Partitions should fit perfectly inside the enclosure unit, with no gap. If there is a gap, use a foam tape to fill it.
Foam tape
Partition
Single enclosure unit
Design the enclosure unit according to the following specifications to keep discharged hot air from flowing back into the
inlet.
•
Air inlet ( )
Total open area of the ventilation holes: 63000
mm or more
Ventilation opening ratio (% of total opening): 70 % or more
•
Air outlet ( )
Total open area of the ventilation holes: 63000
mm or more
Ventilation opening ratio (% of total opening): 70 % or more
–
Design the locations of the enclosure unit inlet and outlet to match the locations of the product inlet and outlet.
Back
Side view
English - 48