Connection of the 3-way valve
3-way diverting valve for water tank
-Diverting type
- 230V AC
N
L
L1
When water pass to floor heating
When water pass to water tank
N
N L1 L
L
L1
Hydro
unit
Water
tank
Floor
heating
3Way Valve
Hydro
unit
Water
tank
Floor
heating
3Way Valve
N
N
L
L1
L
Description
No. of wires
Max. A
Thickness
Supply Scope
Diverting type 3way valve
4
22mA
0.75mm
2
H05RN-F
or H07RN-F
Field supply (230V~, Output)
1. Before the installation, hydro unit should be
turned off.
2. Using the appropriate equipment to correct
position of terminal block as shown on the
diagram.
3. Make sure what type of 3 way V/V you use .
Process
Connection of the back-up boiler
Description
No. of wires
Max. A
Thickness
Supply Scope
Back-up Boiler
2+ground
1 A
0.75mm
2
H05RN-F
or H07RN-F
Field supply (230V~, Output)
L
N
Boiler
N
When it set back up
boiler on the hydro unit
(relay off)
L
N
Boiler
N L
When it order to
back up boiler operates
(relay on)
1. Before the installation, hydro unit should be
turned off.
2. Using the appropriate equipment to correct
position of terminal block as shown on the
diagram.
3. Make sure EXT-CTRL signal of back up boiler
must be 230Vac.
◆
Do not connect supply power of back up
boiler directly.
Process
Connection of the solar circulation pump for DHW tank
Description
No. of wires
Max. A
Thickness
Supply Scope
Solar pump
2+ground
1 A
0.75mm
2
H05RN-F
or H07RN-F
Field supply (230V~, Input)
Solar pump
Solar pump
In non-operating mode,
No signal to Hydro unit
L
N
N L
In operating mode,
On-signal to Hydro unit
N L
1. Before the installation, hydro unit should be turned off.
2. Using the appropriate equipment to correct position of terminal
block as shown on the diagram.
3. It is for hydro unit to inform that the pump is operating.
4. Solar pump is controlled by installer’s handling. And it send the
signal to hydro unit depending on solar pump conditions.
In operating mode, signal shall be around 230Vac B/W N&L.
In non-operating mode, signal shall be around 0Vac B/W N&L.
Process
Wiring work (Continued)