E-
42
DHW tank (Continued)
System configuration
For the reliable performance and durability, all parts as listed below ,including a relief valve, an
expansion vessel, a drain valve and pressure reducing valve , should be installed according to each
national or regional standards. They are not supplied by SAMSUNG.
- Pressure relief valve (9 bar)
- Expansion vessel (pre-charge pressure = 8 bar)
- Drain valve (manual type)
- Tundish
- Expansion relief valve
- Pressure reducing valve
Screw the thermistor socket in the foreseen threaded thermistor hole in the tank, use a thread sealant
such as Teflon or similar to make water tight.
Apply contact glue to the thermistor and insert the thermistor as deep as possible in the thermistor
socket. Fix using the nut provided.
NH080PHXEAHydro unit_IM_E 32659-1.indd 42
2010-07-28 ソタネト 8:59:51