Troubleshooting

  If an error occurs during the operation, an LED flickers and the operation is stopped except the LED.

  If you re-operate the air conditioner, it operates normally at first, then detect an error again.

Detection of errors

LED Display on the receiver & display unit

LED Display

 

On      Flickering      Off

  If you turn off the air conditioner when the LED is flickering, the LED is also turned off.

  If you re-operate the air conditioner, it operates normally at first, then detect an error again.

Abnormal conditions

Indicators

Operating

Concealed Type

Green

Red

Standard Type

Power reset
Error of temperature sensor in indoor unit  

(OPEN/SHORT)

Displayed on appropriate 

indoor unit which is operating

Error of heat exchanger sensor in indoor unit 

Error of heat exchanger OUT sensor in  

indoor unit 

Error of outlet temperature sensor in  

indoor unit  

(OPEN/SHORT): For heat pump models only

Displayed on appropriate 

indoor unit which is operating

Error of outdoor temperature sensor 

Error of COND sensor 

Error of DISCHARGE sensor

Displayed on appropriate 

indoor unit which is operating 

Displayed on outdoor unit

1.  No communication for 2 minutes between 

indoor unit and outdoor unit (communica-

tion error for more than 2 minutes)

2.  Indoor unit receiving the communication 

error from outdoor unit

3. Outdoor unit tracking 3 minute error
4.  When sending the communication error 

from outdoor unit the mismatching of the  

communication numbers and installed  

numbers after completion of tracking.  

(communication error for more than  

2 minutes)

1.  Error of indoor unit: 

Displayed on the indoor unit 

regardless of operation

2.  Error of outdoor unit: 

Displayed on the indoor unit 

which is operating

AVXDU@@_IM_E_33764A-1_110621.indd   25

2011-06-23   오전 10:14:36

Summary of Contents for ND220HHXEA

Page 1: ...sibilities Thank you for purchasing this Samsung product To receive more complete service please register your product at www samsung com register Duct Type Series BIG duct ND HH E DB98 33764A 1 AVXDU...

Page 2: ...t 10 Connecting the Refrigerant Pipe 10 Cutting Flaring the Pipes 11 Performing Leak Test Insulation 12 Drain pipe and Drain hose Installation 14 Wiring Work 18 Indoor Unit Setting 22 Additional Funct...

Page 3: ...ccessible to the general public This appliance should be installed according to the provided installation instruction When installing the air conditioner in a small room the measure not to exceed the...

Page 4: ...c work must be done by service agent or similarly qualified persons according to national wiring regulations and use only rated cable If the capacity of the power cable is insufficient or electric wor...

Page 5: ...due to the ballast of the lighting apparatus Do not install the air conditioner in following places Place where there is mineral oil or arsenic acid Resin parts flame and the accessories may drop or w...

Page 6: ...tity may differ depending on the specifications User s manual Installation manual Pattern sheet Insulation cover pipe out Insulation pipe A Insulation pipe B Washer Clamp hose Flexible hose Cable tie...

Page 7: ...ake service clean and repair the unit It is possible to install the unit at an height of between 2 2 2 5m from the ground if the unit has a duct with a well defined lenght 300mm or more to avoid fan m...

Page 8: ...Power supply Communication connection Air discharge grille flange Air suction flange Hook 3 8 or M10 Selecting the Installation Location Continued 140X8 1120 1306 Suspension position 1188 Air inlet d...

Page 9: ...ension bolts between two nuts Screw the nuts to suspend the unit Adjust level of the unit by using measurement plate for all 4 sides Since the diagram is made of paper it may shrink or stretch slightl...

Page 10: ...l A There are two refrigerant pipes of differing diameters A smaller one for the liquid refrigerant A larger one for the gas refrigerant The inside of copper pipe must be clean has no dust The connect...

Page 11: ...er D mm A mm Flaretoolfor R410Aclutchtype Conventional flare tool Clutch type Wing nut type 6 35 0 0 5 1 0 1 5 1 5 2 0 9 52 0 0 5 1 0 1 5 1 5 2 0 12 70 0 0 5 1 0 1 5 1 5 2 0 15 88 0 0 5 1 0 1 5 1 5 2...

Page 12: ...lonitrile Butadien Rubber separately around each refrigerant pipe Note Always make the seam of pipes face upwards 2 Wind insulating tape around the pipes and drain hose avoiding to compress the insula...

Page 13: ...22 23 25 40 28 58 32t 31 75 38 10 44 45 50 80 25t 38t Refrigerant pipe before EEV kit and MCU or without EEV kit and MCU You can contact the gas side and liquid side pipes but the pipes should not be...

Page 14: ...lightly bigger than the external diameter of the drain hose port 4 Wrap the drain hose with the insulation drain as shown in figure and secure it Fix the flexible hose to the indoor unit with the supp...

Page 15: ...slope of 1 100 or more and fix it by hanger space of 1 0 1 5m 3 Install the air vent in the horizontal drain pipe to prevent water flow back to the indoor unit You may not need to install it if there...

Page 16: ...in air vent at the front of the farthest indoor unit from the main drain when installed indoor units are more than 3 2 You may need to install individual air vent to prevent water flow back at the top...

Page 17: ...rain pump pumping 3 Testing the drainage Confirm that the water flows out through the drain hose 2 Reassemble the cover of water supply intake 6 Check drain water drops at the end of the drain pipe 4...

Page 18: ...communication when installing the wired remote control Power and communication cable connection WiringWork Connecting power for optional product When installing optional product make sure to follow b...

Page 19: ...installation manual about the rating current of indoor unit Decide the power cable specification and maximum length within 10 power drop among indoor units T coef 1 55 T Lk Distance among each indoor...

Page 20: ...Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 h Calculation Installing with 1 sort wire 220 V 2 2 V 2 0 V 2 5 mm2 208 8 V Within 198V 242V 2 2 2 0 1 8 1 5 1 3 1 1 0 9 0 7 0 4 0 2 11 2 V it s oka...

Page 21: ...ection from the power supply must be incorporated in the fixed wiring 3mm You must keep the cable in a protection tube Keep distances of 50mm or more between power cable and communication cable Maximu...

Page 22: ...the indoor unit address on the plan that you are to install and set the address according to the plan Setting RMC Address The SW03 and SW04 RMC switch is the address setting switch for controlling th...

Page 23: ...K10K11K12 No Function ON OFF SW06 K5 Heating CurrentTemperature Compensation 2 C 5 C K6 Filter Time 1 000 hours 2 000 hours K7 Hot Water Heater Not Use Use K8 K5K6K7K8 K1K2K3K4 No Function ON OFF SW05...

Page 24: ...stallation of the air conditioner you should explain the following to the user Refer to appropriate pages in the User s Manual 1 How to start and stop the air conditioner 2 How to select the modes and...

Page 25: ...ger OUT sensor in indoor unit Error of outlet temperature sensor in indoor unit OPEN SHORT For heat pump models only Displayed on appropriate indoor unit which is operating Error of outdoor temperatur...

Page 26: ...HARGE 9 COMP DOWN due to 2nd detection of low pressure switch 10 Error of reverse phase 11 Compressor down due to 6th detection of freezing 12 Self diagnosis of condensation sensor G8 G9 13 Compressor...

Page 27: ...ernal static pressure of the installation place is in When it is out of input the appropriate option code If you input the inappropriate option code error may occur or the air conditioner is out of or...

Page 28: ...EEE Y netmeli ine Uygundur This EEE is compliant with RoHS AVXDU _IM_E_33764A 1_110621 indd 28 2011 06 23 10 14 37...

Reviews: