ENGLISH-16
Wired remote controller installation/service mode
additional functions of your wired remote controller
• If communication initialization is needed after the setting, the system will reset automatically and
communication will be initialized .
NOtE
Main
menu
Sub
menu
Function description
Setting value
Page
Save location
Value
Factory default
1
1
Wired remote
controller
setting/
checking (1)
Cooling/Heating selection
0 - Cooling/Heating,
1 - Cooling only
0
01
Wired remote controller
Use of wireless remote controller
for indoor unit
0 - No use, 1 - Use
1
02
Wired remote controller
Master/Slave wired remote
controller
0 - Master, 1 - Slave
0
03
Wired remote controller
Temperature unit
0 - Celsius(°C),
1 - Fahrenheit(°F)
0
04
Wired remote controller
2
Wired remote
controller
setting/
checking (2)
Temperature sensor selection
0 - Indoor unit,
1-Wired remote
controller
0
01
Wired remote controller
Use of average temperature
0 - No use, 1 - Use
0
02
Wired remote controller
Use of Auto mode
0 - No use, 1 - Use
1
03
Wired remote controller
Temperature display
0 - Set temperature
1 - Room
temperature
2 - Relative
temperature 1)*
0
04
Wired remote controller
5
Room
temperature
compensation
2)*
Temperature control reference
-9 ~ 40 °C
Current sensor
temperature
01
Wired remote controller
Temperature compensation value -9 .9 ~ 9 .9 °C
0
02,03 Wired remote controller
6
Number of
connected
units
Number of indoor units
0 ~ 16
0
01
None
7
Temperature increment/decrement unit
(°C only)
0 - 1 °C, 1 - 0 .5 °C, 2 -
0 .1 °C
0
01
Wired remote controller
0
Factory option setting
0 - Unchanged,
1 - Factory setting
0
01
None
2
1
Software code
Software code
None
01~03
None
2
Software version
Software version
None
01~03
None
4
1
Indoor unit
address/
option setting/
checking 3)*
Target address setting
Target address of
indoor unit (Example
: 20 02 1F)
View master
01~03
None
2
Main address setting/checking
0~4F (in hexadecimal
digits)
Main address of
target
01
None
3
RMC address setting/checking
0x00~0xFE 4)*
RMC address of
target
01
None
4
Basic option setting/checking
Option code
Basic option
of target
01~20
5)*
None
5
Install option setting/checking
Option code
Install option of
target
01~20
5)*
None
6
Install(2) option setting/checking Option code
Install(2) option
of target
01~20
5)*