26
Field setting mode
English
Fiel
d S
etting Mode
Field Setting Value (FSV) 20**
Code 20** : Water law design and external room thermostat Heating(2 WL’s for floor & FCU),
Cooling(2 WL’s for floor & FCU), WL & Thermostat types
࡙
The values in the following table are just examples for your understanding.
Main Menu &
Code
Menu
Function
Sub
Code
MODEL CODE :
AE200(260)RNW***
MODEL CODE :
MIM-E03CN /
MIM-E03EN
Setting Standard
Setting Standard
Item
Step Unit
Default Min. Max. Default Min.
Max.
Water Law
Code 20**
Heating
Outdoor Temperature for
Heating Water Law
Max (Point
1
)
1
ঐ
2011
-10
-20
5
-10
-20
5
Min (Point
2
)
1
ঐ
2012
15
10
20
15
10
20
Water out
Temperature for
WL1 Heating (UFHs)
Max (Point
1
)
1
ঐ
2021
40
17 65/70
1)*
40
17
65/70
1)*
Min (Point
2
)
1
ঐ
2022
25
17 65/70
1)*
25
17
65/70
1)*
Water out
Temperature for
WL2 Heating (FCUs)
Max (Point
1
)
1
ঐ
2031
50
17 65/70
1)*
50
17
65/70
1)*
Min (Point
2
)
1
ঐ
2032
35
17 65/70
1)*
35
17
65/70
1)*
Heating Water Law
Selection
WL Type
-
- 2041 1(WL1)
1
2
1 (WL1)
1
2
Cooling
Outdoor Temperature
for
Cooling Water Law
Max (Point
1
)
1
ঐ
2051
30
25
35
30
25
35
Min (Point
2
)
1
ঐ
2052
40
35
45
40
35
45
Water out
Temperature for
WL1 Cooling (UFHs)
Max (Point
1
)
1
ঐ
2061
25
5
25
25
5
25
Min (Point
2
)
1
ঐ
2062
ߢߩ
5
25
ߢߩ
5
25
Water out
Temperature for
WL2 Cooling (FCUs)
Max (Point
1
)
1
ঐ
2071
ߢߩ
5
25
ߢߩ
5
25
Min (Point
2
)
1
ঐ
2072
5
5
25
5
5
25
Cooling Water Law
Selection
WL Type
-
-
ߣߡߩߢ
1(WL1)
1
2
1(WL1)
1
2
External
Control
External Room
Thermister
#1 (UFHs)
1
- 2091 0(No)
0
4
0(No)
0
4
#2 (FCUs)
1
- 2092 0(No)
0
4
0(No)
0
4
Remote
Controller
Remote Controller Room Temp. Control
1
- 2093
4
1
4
4
1
4
NOTE
࡙
1)*
The value is determined according to the type of outdoor unit.