2way valve for zone 2
2way valve (#3)
Connecting 2way valve (for Zone2 )
1. Directly connect ‘2way valve for ZONE.1’ with ‘pin #15, 16, 17, 18’ in TB-B.
f
f
If control kit orders opening Water Pump on, pin#15 & pin#17 will output AC230V.
Maximum Power
This port can supply power for small-medium sized valve.
Maximum power is 0.5A
(If total power consumption is over 2A, use relay or magnetic contactor)
NOTE
Specification table
Part
Specification
Connection pin
#15 : Output Power N
#16 : Output Power L
#17 : Output turning on Power (Normal Opened L line)
#18 : Output turning on Power (Normal Closed L line)
Connection load
Direct connect 2way valves (under 0.5A)
Output
AC 230V (MAX 0.5A / 120W)
Condition for operation
(NOT Define)
Wiring works
Example of valve connection
f
f
2 pole (L1, N) type
• L1 port of Valve is connected to #13
• N port of Valve is connected to #11
(If L1, N ports of Valve get power, water can flow to Zone1.)
(If L1, N ports of Valve don`t get power, water can NOT flow to Zone1.)
f
f
3 pole (L, L1, N) type
• L port of Valve is connected to #12
• L1 port of Valve is connected to #13
• N port of Valve is connected to #11
(If L1, N ports of Valve get power, water can flow to Zone1.)
(If L1, N ports of Valve don`t get power, water can NOT flow to Zone1.)
f
f
4 pole (L, L1, /L1
*1)
, N) type
• L port of Valve is connected to #12
• L1 port of Valve is connected to #13
• /L1
*1)
port of Valve is connected to #14
• N port of Valve is connected to #11
(If L1, N port of Valve get power, water can flow to Zone1.)
(If /L1
*1)
, N port of Valve get power, water can NOT flow to Zone1.)
*1) /L1 means opposite side signal of L1.