background image

Password Reset

1 .  Access to main menu by pressing the [Menu] button from the normal display . Then select ‘2 .Configuration’ by pressing 

the [

], [

] buttons, and press [Set] button .

Main Menu
2.Configuration

2 .  Enter the password using the [

], [

] buttons and press the [Set] button . 

 - The default password is ‘0000’ .

Enter your P/W
0:0:0:0

3 .  Select ‘2 .1 Password’ by pressing the [Set] button .

2.Configuration
2.1 Password

4 .  Select ‘Password Reset’ by pressing the [Set] button to reset the password .

2.1 Password
Password Reset

5 .  Press the [Set] button to reset the password . To cancel resetting, press the [Menu] button .

 - If you press the [Set] button, the password will reset to ‘0000’ .

Are you sure ? 
YES:Set, NO:Menu

Password Reset
0:0:0:0

6 .  After the setting, press the [Menu] button to move to upper menu or cancel the setting .

 - All menus will return to the normal display if there is no input for 1 minute .

English-21

INST
All

ING
 Th

E PRODUC

T

02

MIM-B16N_PIM_IM_DB68-04502A-03_EN.indd   21

2016-10-19   오후 3:19:28

Summary of Contents for MIM-B16N

Page 1: ...PIM Pulse Input Module MIM B16N Air Conditioner installation manual imagine the possibilities ThankyouforpurchasingthisSamsungproduct MIM B16N_PIM_IM_DB68 04502A 03_EN indd 1 2016 10 19 오후 3 19 22 ...

Page 2: ...y Precautions 3 Accessories 4 Viewing the Parts 5 PIM System Architecture 8 Installing the product Installing the PIM 9 Setting the PIM 15 PIM Menu Description 16 English 2 MIM B16N_PIM_IM_DB68 04502A 03_EN indd 2 2016 10 19 오후 3 19 22 ...

Page 3: ... the PIM with rated power supply f f The PIM must be installed according to the national electrical rules by an installation specialist f f If you wish to uninstall the PIM consult an authorized installation center CAUTION f f Do not use inflammable gases near the PIM f f Do not install the PIM in a location where it will come into contact with combustible gases machine oil sulphide gas etc f f Av...

Page 4: ...al Cable tie Quantity 1 1 1 6 1 1 Shape The PIM must be installed by a trained installer Ensure the main power is turned off before installing the PIM Be sure to use adapter and power cable we provide The power cable and the communication cable must be installed according to the national electrical wiring regulations Use 2C x 0 75mm2 communication cable CAUTION English 4 MIM B16N_PIM_IM_DB68 04502...

Page 5: ... separate the bottom cover from PIM Then check cable connection part Explanation of LED Indicator Item Name Status Power Power indicator Turns blue when the power is supplied COM1TX RX Data transmission reception with DMS indicator Blinks in orange during the normal transmission reception Signal 1 8 Input pulse indicator Blinks in orange when a normal pulse is input from the meter COM2TX RX Reserv...

Page 6: ...Terminal that the pulse from Meter is inputted Channel1 Channel8 Dry contact must be connected Power terminal Terminal to connect PIM adapter Reset button Button used to reset PIM RS485 Communication terminal COM1 Connection terminal for RS485 communication with DMS COM2 Not in use It will be used for MODBUS in the future Cable groove Groove for arranging cables English 6 MIM B16N_PIM_IM_DB68 0450...

Page 7: ...terior LED Display board 40 pin cable 20 pin cable Main board Sub board Product Dimensions 240 255 64 8 Unit mm English 7 Before installation 01 MIM B16N_PIM_IM_DB68 04502A 03_EN indd 7 2016 10 19 오후 3 19 24 ...

Page 8: ...ter max 8 units ROOM 0 ROOM 1 ROOM 2 Outdoor Unit Pulse input f f Maximum 8 PIM units can be connected to DMS f f Maximum 8 meter Power Gas Water can be connected to PIM English 8 MIM B16N_PIM_IM_DB68 04502A 03_EN indd 8 2016 10 19 오후 3 19 24 ...

Page 9: ... 2 screws Depending on the installation environment open the top cover and fix PIM using assistant holes Screws for assistant hole are not provided Assistant hole 5 If you install PIM inside of the wall or wiring from the rear side is needed use wiring groove on the bottom of PIM Wiring groove To prevent breakdown and damage of PIM and for safe usage it is recommended to install PIM on the wall CA...

Page 10: ...y as you want In this step use communication cable and 8 terminal blocks which are attached to the pulse input terminal of PIM For the communication cable connection instruction of a Meter or additional setting instruction refer to the installation manual of a Meter Connect the communication cable considering the polarity Left Right Connect communication cable Meter Maximum 8 meter Power Gas Water...

Page 11: ... possible Meter with Separate External Output f f Connect according to the pulse output specification Meter must have more than 4ms Delay Between the First Pulse Input and the Next Pulse 20 1000ms Waveform of CH1 8 Over 4ms Limit of Connectable Meter Pulse constant range Power 1Wh Pulse 10 000Wh Pulse Gas 0 001m3 Pulse 10m3 Pulse Water 1L Pulse 10 000L Pulse Pulse width range 20 1000ms CAUTION Nex...

Page 12: ...PIM A of DMS B of PIM B of DMS Connect communication cable Connect communication cable PIM DMS A B 2 Close the bottom cover and fix it using 2 screws f f When execute tracking with PIM which connected to DMS Displays the number of SIM or PIM A name of a PIM For the further information about tracking refer to the DMS user manual English 12 MIM B16N_PIM_IM_DB68 04502A 03_EN indd 12 2016 10 19 오후 3 1...

Page 13: ...f f If PIM is connected to DMS PIM setting through DMS web is possible English 13 Installing the product 02 MIM B16N_PIM_IM_DB68 04502A 03_EN indd 13 2016 10 19 오후 3 19 26 ...

Page 14: ... are assigned for system extension in the future Therefore do not set the addresses as they will not be recognized with a DMS 9 N A 9 39H A N A A 3AH B N A B 3BH C N A C 3CH D N A D 3DH E N A E 3EH F N A F 3FH 3 Close the top PIM cover and fix it using 2 screws Error Codes Display Explanation E613 Error which occurs when there is no communication between DMS and PIM for 15 minutes E632 Error which...

Page 15: ... further information refer to page 24 25 f f The display above is an example Setting for the Connected meter type and pulse rate Setting the meter type 2 Configuratuion 2 2 Meter Type 2 2 Meter Type CH1 Power Meter Main menu 2 Configuration 2 2 MeterType f f For the further information refer to page 22 Setting the meter pulse rate 2 Configuratuion 2 3 Pulse Rate 2 3 Pulse Rate CH1 00100Wh P Main m...

Page 16: ...eck 2 Configuration 2 1 Password 2 2 Meter Type 2 3 Pulse Rate 2 4 Date Time 2 5 Channel Use 2 6 Value Set 2 7 Value Clear 3 1 Pulse Input 3 2 COM Check 3 3 Pulse Width CH1 00000 0kWh CH2 00000 0kWh CH8 00000 0kWh Normal Display Displayed repeatedly English 16 MIM B16N_PIM_IM_DB68 04502A 03_EN indd 16 2016 10 19 오후 3 19 26 ...

Page 17: ...Addr 58 30 FF Device Info DBC DB91 01128A 2 Consumption of pulse input CH1 CH8 will be displayed in order CH1 00000 0kWh CH2 00000 0kWh 3 Current time will be displayed after the consumption of CH8 It displays CH1 CH8 and current time repeatedly You can make the display stop moving with using Set button for easy view You can find which channel you want to see with using the buttons English 17 Inst...

Page 18: ...fter checking press the Menu button to move to upper menu or cancel the setting All menus will return to the normal display if there is no input for 1 minute Option Switch For monitoring only 1 Access to main menu by pressing the Menu button from the normal display Then select 1 Monitoring by pressing the Set button 1 Monitoring 1 2 Option S W 2 Move to 1 2 Option S W menu by pressing the buttons ...

Page 19: ...the normal display if there is no input for 1 minute DB Code 1 Access to main menu by pressing the Menu button from the normal display Then select 1 Monitoring by pressing the Set button Main Menu 1 Monitoring 2 To check the DB Code press the Set button when 1 4 DB Code appears 1 Monitoring 1 4 DB Code 1 4 DB Code DB91 01128A NOTE DB91 01128A is an example 3 After checking press the Menu button to...

Page 20: ...ord is 0000 Enter your P W 0 0 0 0 3 Select 2 1 Password by pressing the Set button 2 Configuration 2 1 Password 4 Select Password Set by pressing the Set button to set the new password 2 1 Password Password Set 5 Set the new password using the buttons and press the Set button Set your P W 6 Press the Set button to save the setting Save Settings 0 0 0 0 7 After the setting press the Menu button to...

Page 21: ... Password 4 Select Password Reset by pressing the Set button to reset the password 2 1 Password Password Reset 5 Press the Set button to reset the password To cancel resetting press the Menu button If you press the Set button the password will reset to 0000 Are you sure YES Set NO Menu Password Reset 0 0 0 0 6 After the setting press the Menu button to move to upper menu or cancel the setting All ...

Page 22: ...ve to the channel you want to set by pressing the buttons and then press the Set button You can select each channel or all channel altogether 2 2 Meter Type CH1 Power Meter 5 Modify the meter type by pressing the buttons Dafult value Power Meter Type Power Meter Gas meter Water Meter To apply same type of the meter to all channels at once select ALL Channel in step 4 Set CH1 Meter CH1 Power Meter ...

Page 23: ...e 4 Move to the channel you want to set by pressing the buttons and then press the Set button You can select each channel or all channel altogether 2 3 Pulse Rate CH1 00001Wh P 5 Modify the digit by pressing the buttons You can move to the next digit by pressing the Set button Default Power 1Wh P Gas 0 001m3 P Water 1L P Constant range Power 1Wh P 10 000Wh P Gas 0 001m3 P 10m3 P Water 1L P 10 000L...

Page 24: ...ng the Set button 5 Previously set date will be displayed Press the Set button to set the current date Y M D Press the Menu button to return to the upper menu Current Date 2010 01 05 6 Modify the date in order of year month and day by pressing the buttons You can move to the next item by pressing the Set button Set Current Date 2010 01 05 7 Press the Set button to save the setting Press the Menu b...

Page 25: ...sly set time will be displayed Press the Set button to set the current time H M S Press the Menu button to return to the upper menu Current Time 11 25 14 PM 6 Modify the date in order of hour minute and second by pressing the buttons You can move to the next item by pressing the Set button Set Current Time 11 25 09 PM 7 Press the Set button to save the setting Press the Menu button to return to th...

Page 26: ...o the channel you want to set by pressing the buttons and then press the Set button You can select each channel or all channel altogether 2 5 Channel Use Channel1 En 5 Enable Press the Set button when Enable Channel appears Disable Press the buttons and then press Set button when Disable Channel appears To enable disable all channels select ALL in step 4 Disabled channel will not be displayed on t...

Page 27: ...t button You can select each channel or all channel altogether 5 Modify the digit by pressing the buttons You can move to next digit by pressing the Set button You can modify the initial value of the channel you wish to change If you modify the setting saved value will be reset and the device will re calculate the value according to the modified value To set the initial value for all channels sele...

Page 28: ...e buttons and then press the Set button You can select each channel or all channel altogether 2 7 Value Clear CH1 00000 0kWh 5 Press the Set button to initialize the selected channel when the caution message appears Clear Initializes the consumption calculated so far To cancel the initialization press the Menu button To initialize all channels you can select ALL Channel in step 4 Are you Sure YES ...

Page 29: ...ulse Input CH1 Check OK CH1 Check Start Checking 4 The result regarding the pulse input of the channel will be displayed OK NG NG will be displayed when there is no input within 10 seconds after selecting the channel If the pulse input is normal Displayed in number If there is no pulse input Displayed X CH1 3 4 6 8 No pulse input CH2 5 7 OK PIM does not calculate the consumption during the inspect...

Page 30: ...ng the buttons and press the Set button Main Menu 3 Check 2 Select 3 2 COM Check by pressing the buttons and then press the Set button Inspect the packet transmission reception status with DMS 3 Check 3 2 COM Check COM Check Start Checking 3 Communication inspection result will be displayed OK NG COM Check End OK 4 After the inspection press the Menu button to move to upper menu or cancel the sett...

Page 31: ... Checking 4 The result of pulse input for the selected channel will be displayed OK NG setting measurement OK When the pulse is valid pulse is valid when high pulse between 20 1000msec OK M msec will be displayed represent the duration of the high pulse NG When the pulse is invalid pulse is valid when high pulse is between 20 1000msec or when there s no pulse input for 10 seconds NG M 0000msec wil...

Page 32: ...DB68 04502A 03 MIM B16N_PIM_IM_DB68 04502A 03_EN indd 32 2016 10 19 오후 3 19 30 ...

Reviews: