Installing the PIM
Installing more than 2 PIM Units to 1 DMS
1 . Unfasten the 2 screws on the top of the PIM . Hold the top 2 sides of the PIM and
pull it the cover upwards to open the cover .
2 . Set the PIM address using rotary switch of main PCB . (Default setting: 30H)
- Rotary Switch #1 : Not in use
- Rotary Switch #2 : 0 ~ F (30H ~ 3FH)
Rotary
Switch #1
Communication
Address
Rotary
Switch #2
Communication
Address
DMS Address
0
N/A
0
30H
16
1
N/A
1
31H
17
2
N/A
2
32H
18
3
N/A
3
33H
19
4
N/A
4
34H
20
5
N/A
5
35H
21
6
N/A
6
36H
22
7
N/A
7
37H
23
8
N/A
8
38H
❋
❋
The PIM communication
addresses on the left
side (8~F) are assigned
for system extension in
the future . Therefore, do
not set the addresses
as they will not be
recognized with a DMS .
9
N/A
9
39H
A
N/A
A
3AH
B
N/A
B
3BH
C
N/A
C
3CH
D
N/A
D
3DH
E
N/A
E
3EH
F
N/A
F
3FH
3 . Close the top PIM cover and fix it using 2 screws .
Error Codes
Display
Explanation
E613
Error which occurs when there is no communication between DMS and PIM for 15 minutes .
E632
• Error which occurs when the pulse was input differently from the PIM setting .
• (If the pulse was inputted at the value outside of 10 ms ~ 1500 ms range for more than 15 times or when
high pulse was inputted for over 3 minutes)
E654
Memory Read/Write error .
E108
Error which occurs when same address was assigned to different devices .
English-14