11

ENGLISH

DO port

f

f

DO operation specification

DO output will turn on if any one of the indoor unit is turned on. DO output will 
turn off if all the indoor units are turned off.

f

f

DO port

(+)terminal outputs 12 V, (-) terminal outputs open collector, Drive current 
under 10 mA.

DO (+,-)

Touch-controller_IM_03943A_1_EN.indd   11

2013-06-28   오후 3:07:05

Summary of Contents for MCM-A300N

Page 1: ...Touch controller_IM_03943A_1_Co_EN indd 2 2013 06 28 오후 3 06 00 ...

Page 2: ...itioner installation manual imagine the possibilities Thank you for purchasing this Samsung product DB68 03943A 1 EN ES FR IT PT DE EL RU AR This manual is made with 100 recycled paper Touch controller_IM_03943A_1_Co_EN indd 3 2013 06 28 오후 3 06 00 ...

Page 3: ...ith rated voltage when installing f f If not there is risk of fire or damage to the product Do not attempt to move or re install the product that is already installed f f There is risk of electric shock and fire Do not attempt to repair disassemble or modify the product yourself f f There is potential risk of product damage electric shock or fire When repair is needed consult qualified installer o...

Page 4: ...ation f f Cable may get cut and cause fire Install the product in a place with temperature between 0 c 39 c with no direct sunlight f f There is risk of electric shock or abnormal operation Do not install the product in a place where special spray or acid alkali solution is used f f There is risk of electric shock or abnormal operation Do not press the button with sharp object f f There is risk of...

Page 5: ... prior notice Name Touch Centralized Controller Cable tie M4 Screw User s manual Installation manual Quantity 1 3 4 1 1 Image Touch Centralized Controller must be installed by the installation expert Before installing theTouch Centralized Controller check if the power is off Communication cable must be installed according to the electrical wiring regulation and make sure that cable is installed th...

Page 6: ...Silver solder Nominal dimensions for cable mm2 1 5 2 5 Nominal dimensions for screw mm 4 4 4 4 B Standard dimension mm 6 6 8 6 6 8 5 Allowance mm 0 2 0 2 D Standard dimension mm 3 4 4 2 Allowance mm 0 3 0 2 0 3 0 2 d1 Standard dimension mm 1 7 2 3 Allowance mm 0 2 0 2 E Min mm 4 1 6 F Min mm 6 6 L Max mm 16 17 5 d2 Standard dimension mm 4 3 4 3 Allowance mm 0 2 0 0 2 0 t Min mm 0 7 0 8 Touch contr...

Page 7: ...ntroller Control Monitoring Schedule Setting SD card slot LCD ON OFF button Indoor unit operation lamp Blue Error lamp Red Bottom Power terminal DI 1 terminal Reset Button DI 2 terminal RS 485 communication terminal DOTerminal Touch controller_IM_03943A_1_EN indd 6 2013 06 28 오후 3 07 03 ...

Page 8: ...7 ENGLISH Product dimensions 203 170 Unit mm 161 38 141 Touch controller_IM_03943A_1_EN indd 7 2013 06 28 오후 3 07 04 ...

Page 9: ... turns on If the LCD does not turn on check the connection of the power AC 100 240V 50 60 Hz terminal and the power connector Checking the LED 1 There is an error If the Error lamp Red turns on 2 If the Error lamp Red turns on check the connection status of communication power and the status of communication cable 3 If the Error lamp Red turns on check if there is any error on the indoor unit that...

Page 10: ...t done properly communication may not work properly Use appropriate tools to connect the cables firmly within rated torque range so that it can withstand external forces You may connect the communication cable of the F1 F2 terminal of the indoor outdoor unit or R1 R2 of the outdoor unit When connecting theTouch Centralized Controller to indoor outdoor unit layer use F1 F2 terminal and use R1 R2 te...

Page 11: ... 1 DI 2 Control pattern Pattern Description of control 1 No external input Factory default setting Nothing will happen when contact signal is inputted to port 1 2 When DI 1 ON signal is input emergency stop status will occur It will stop all indoor units and order the indoor units not to be controlled by a remote controller In the emergency stop status you cannot use the user control command In ad...

Page 12: ...urn on if any one of the indoor unit is turned on DO output will turn off if all the indoor units are turned off f f DO port terminal outputs 12V terminal outputs open collector Drive current under 10 mA DO Touch controller_IM_03943A_1_EN indd 11 2013 06 28 오후 3 07 05 ...