Additional refrigerant
10. Installation
Refrigerant pipe installation
•
Basic amount of refrigerant within the outdoor unit [lb(kg)]
– Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
•
Amount of additional refrigerant depending on the pipe size (
ⓐ
)
– Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
– For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.0067lb/ft (0.01kg/m)
regardless of the pipe size.
1/2” (5m/16.4’)
1/2” (5m/16.4’)
1/2” (5m/16.4’)
1/4” (5m/16.4’)
1/4” (10m/32.8’)
1/4” (15m/49.2’)
3/8”
(10m/32.8’) 3/8”
(10m/32.8’)
3/8” (10m/32.8’)
3/8”
(10m/32.8’)
1/4” (5m/16.4’)
3/8” (10m/32.8’)
1
20
MBH (1
0
Ton)
12MBH
12
MBH
12
MBH
18MBH
18MBH
18MBH
18MBH
12MBH
Classification
AM072BXVT**
AM096BXVT**
AM120BXVT**
Basic amount [lb(kg)]
17.6 (8.0)
23.1 (10.5)
23.1 (10.5)
Size of liquid pipe
[mm (inch)]
ףߣࢩߦ
࣑ףߨߥߧ࣒
ףߥࢩߪ
࣑ף߫ߧߤ࣒
ףߣࢩߤ
࣑ףߣߤߩ࣒
ףߧࢩߪ
࣑ףߣߧߪߪ࣒
ףߥࢩߦ
࣑ףߣ߫ߢߧ࣒
ףߩࢩߪ
࣑ףߤߤߤߤ࣒
ףߣ
࣑ףߤߧߦ࣒
ףߣߣࢩߪ
࣑ףߤߪߧߪ࣒
Additional amount
[lb/ft (kg/m)]
0.013
(0.02)
0.04
(0.06)
0.084
(0.125)
0.121
(0.18)
0.181
(0.27)
0.235
(0.35)
0.356
(0.53)
0.437
(0.65)
Amount of
refrigerant added
when the diameter
of liquid pipe is
reduced
[kg/m (lb/ft)]
-
0.054
(0.08)
0.087
(0.13)
0.131
(0.195)
0.188
(0.28)
0.282
(0.42)
0.356
(0.53)
-