Wired Remote Control
MWR-WW00N

DVM Hydro unit / Hydro unit HT

installation manual

imagine 

the possibilities

Thank you for purchasing this Samsung 
product.

DB68-03973A-06

DVM HT_HE RC-EU_IM_EN_DB68-03973A-06.indd   1

2017-05-25   오후 4:18:26

Summary of Contents for DVM Series

Page 1: ...ntrol MWR WW00N DVM Hydro unit Hydro unit HT installation manual imagine the possibilities Thank you for purchasing this Samsung product DB68 03973A 06 DVM HT_HE RC EU_IM_EN_DB68 03973A 06 indd 1 2017 05 25 오후 4 18 26 ...

Page 2: ...ure to do so may result in product malfunction electric shock and fire When you need to repair the product you should contact a service center All the electric work should be performed in accordance with local regulation and installation manual by a certified technician f f Failure to do so may result in product malfunction electric shock and fire due to defect Install the product on a hard and ev...

Page 3: ...e Do not install the product in specific areas exposed to oil or vapor f f Failure to do so may result in part damage or abnormal operation Do not put undue stress on the power cable f f Failure to do so may result in broken cable and fire Do not install the product in areas where acid or alkali liquid or special spray are used f f Failure to do so may result in electric shock or abnormal operatio...

Page 4: ... a certified technician Check and confirm the power is off before installing your wired remote controller Install the wired remote controller cables in accordance with the electrical wiring regulation and allow it to pass through the inner area of the wall so that other people can t reach it CAUTION External Dimensions 120 4 72 124 4 88 63 8 2 51 19 5 0 76 Unit mm inch DVM HT_HE RC EU_IM_EN_DB68 0...

Page 5: ... flat head screwdriver into the square groove in the upper area of the hook to disassemble it easily 2 Arrange the communication cable so that they fit in the housing along the edges of the rear cover If you need more space for the wiring work you can take it off 15 cm 5 90 When the cable is not concealed When the cable is concealed 10 cm 3 93 DVM HT_HE RC EU_IM_EN_DB68 03973A 06 indd 5 2017 05 25...

Page 6: ...dro unit Hydro unit HT PCB Before fixing the rear cover allow at least 10 mm 0 4 inch space of upper side left side right side and 50 mm 2 inch space of bottom side You must fit the screws into the screw holes Do not tighten the screws on the PCB terminal with excessive force 4 Reassemble your wired remote controller NOTE Align the controller with the upper groove first and insert it by turning it...

Page 7: ...Remote Controller by using two pieces of PVC wire remove the 30 cm 12 inch of the sheath of the cable and install it only with the two pieces of wires Recommended specification AWG20 The followings are the specs of the compressed ring terminal connectable to your wired remote controller PCB W t G E F L Stud D Stud Range of Permitted Wires Rated Size Stud Size Basic Size mm AWG mm2 mm2 mm t øD G E ...

Page 8: ...tion 2 If you want to perform tracking again after installation press the Esc and Delete buttons at the same time for more than 5 seconds f f The system will reset and tracking will start again 3 During the tracking the total number of currently searched Hydro unit Hydro unit HT will be displayed If you want to do system reset for your wired remote controller press the Esc and Delete buttons at th...

Page 9: ...Outdoor unit COM1 F1 F2 COM2 F3 F4 COM2 F3 F4 COM2 F3 F4 COM1 F1 F2 Hydro unit Hydro unit HT Wired remote controller Wired remote controller Wired remote controller Hydro unit Hydro unit HT Hydro unit Hydro unit HT Regardless of the Hydro unit Hydro unit HT group address RMC address setting only the Hydro unit Hydro unit HT connected to COM2 is individually controlled CAUTION DVM HT_HE RC EU_IM_EN...

Page 10: ...Wired remote controller Hydro unit Hydro unit HT Hydro unit Hydro unit HT 2 Using one wired remote controller to control Hydro unit Hydro unit HTs connected to different outdoor unit Outdoor unit Outdoor unit COM1 F1 F2 COM1 F1 F2 COM2 F3 F4 COM2 F3 F4 Hydro unit Hydro unit HT Hydro unit Hydro unit HT Wired remote controller Regardless of the Hydro unit Hydro unit HT group address RMC address only...

Page 11: ...r sensor use please install the master remote controller at indoor places Outdoor unit Wired remote controller Slave COM1 F1 F2 COM2 F3 F4 Hydro unit Hydro unit HT Wired remote controller Master For the slave wired remote controller settings please refer to the sections about the wired remote controller installation service mode Refer to page17 0 Master 1 Slave CAUTION DVM HT_HE RC EU_IM_EN_DB68 0...

Page 12: ...F3 F4 COM1 F1 F2 Hydro unit Hydro unit HT Wired remote controller Hydro unit Hydro unit HT Hydro unit Hydro unit HT Unit No 1 Unit No 2 Unit No 3 Hot water tank sensor Hot water tank ex Unit No Water tank sensor cable wiring 05 Series install option SEG24 setting 1 Connected 0 2 Not connected 1 3 Not connected 1 DVM HT_HE RC EU_IM_EN_DB68 03973A 06 indd 12 2017 05 25 오후 4 18 30 ...

Page 13: ...dro unit HT needs to share the temperature value of the hot water tank it must be connected to the same remote controller that is connected to other hydro unit hydro unit HT that is connected directly to the hot water tank with a temperature sensor Also when there are more than 2 wired remote controllers they should be connected to same communication line When multiple units hydro unit hydro unit ...

Page 14: ...ur wired remote controller again Error display on the wired remote controller The address of Hydro unit is displayed 200000 f f Error codes for the wired remote controller and the product connected to your wired remote controller will be displayed in the LCD display Error indications are displayed as seen below 1 Hydro unit Hydro unit HT error f f The address of Error Ai and the error code will be...

Page 15: ...nit Display Contents Communication error between remote controller and the Hydro unit Hydro unit HT Communication error between master and slave remote controller Tracking error between remote controller and the Hydro unit Hydro unit HT Error due to exceeding maximum numbers of Hydro unit installation 16 units Error due to exceeding maximum numbers of wired remote controller installation 2 units E...

Page 16: ...g screen f f Using the buttons select a sub menu number and press the button to enter data setting screen f f When you enter the setting stage the current setting value will be displayed f f Refer to the chart for data settings f f Using the buttons change the setting value Press the button to move to the next setting value f f Press the Set button to save the setting value and exit to the sub men...

Page 17: ...f connected devices The number of connected device 12 0 0 16 1 5 Setting desired temperature unit Available only when the temperature display is C 1 1 0 1 C 1 0 5 C 2 0 1 C 0 Reset to option setting default value of wiredremote controller 1 0 0 Disuse 1 Reset 2 1 Checking Micom code of wired remote controller 1234 4 Micom code 2 Checking version information of wired remote controller 1234 34 Revis...

Page 18: ...etting screen f f When you enter the setting stage the current setting value will be displayed f f Refer to the chart for data settings f f Using the buttons change the setting value Press the button to move to the next setting value f f Press the Set button to save the setting value and exit to the sub menu setting screen f f Press the ESC button to exit to normal mode When setting the data you c...

Page 19: ...r 2 Current time setting month date 12 34 01 01 1 12 1 31 Month Date 3 Current time setting day hour minute Day AM PM 24 12 34 Fri PM 12 00 Sun Sat AM PM 0 12 0 60 Day hour minute 3 1 Summer time use and setting methods Use of summer time Y N 1 0 0 Disuse 1 Use Summer time application method 2 0 0 Weekly 1 Daily 2 Summer time use weekly Start month th Sunday 12 4 03 F Jan Dec month 1 4 F last week...

Page 20: ...u number and press the button to enter data setting screen f f When you enter the setting stage the current setting value will be displayed f f Refer to the chart for data settings f f Using the buttons change the setting value and press the Set button to save the setting value Setting value will be displayed when it is saved f f Press the button to move previous setting value f f While configurin...

Page 21: ...perature of auto heating leaving water WL2 FCU Max 2031 50 35 50 1 C Min 2032 35 17 50 1 C Auto heating of wired remote controller WL type 2041 1 WL1 1 2 Use of thermostat 2091 0 No 0 2 DHW Activating hot water function DHW application 3011 0 No 0 1 Yes Heating mode Max 3021 50 45 50 1 C Stop 3022 2 0 10 1 C Start 3023 5 5 20 1 C Minimum heating operation time 3024 5 1 20 1 min DHW operation time ...

Page 22: ...ature 5014 16 16 30 1 C Temperature of auto heatingWL1 water 5017 15 15 50 1 C Temperature of auto heatingWL2 water 5018 15 15 50 1 C Temperature of hot waterTank 5019 30 30 75 1 C Economic DHW mode Temperature of hot waterTank 5021 5 0 40 1 C Smart grid Power peak control Operation 5041 0 No 0 1 Yes Heat source for operation limit 5042 0 All 0 2 1 Contact Logic 5043 1 High 0 Low 1 Ratio of hot wa...

Page 23: ...g of wired remote controller WL type 2041 1 WL1 1 2 Use of thermostat 2091 0 No 0 2 DHW Activating hot water function DHW application 3011 0 No 0 1 Yes Heating mode Max 3021 70 45 75 1 C Stop 3022 2 0 10 1 C Start 3023 5 5 20 1 C Minimum Heating Operation time 3024 5 1 20 1 min DHW operation time 3025 30 5 95 5 min Heating operation time 3026 3 0 5 10 0 5 hour Booster heater Operation 3031 1 On 0 ...

Page 24: ...ng to field specification f f Code 10 Upper and lower temperature limits for Heating Water out Room Cooling Water out room DHW Tank mode 1011 MaximumValue of cooling leaving water temperature setting in wired remote controller 1012 MinimumValue of cooling leaving water temperature setting in wired remote controller 1021 MaximumValue of cooling indoor s room temperature setting in wired remote cont...

Page 25: ...plication of DHW tank 302 Heat pump variables for tank temp control and combination with booster heater 3021 Maximum DHW tank temperature with heat pump H P operation 3022 Offset temperature of forced DHW s thermo off Only Hydro Unit Not Hydro Unit HT Forced DHW s thermo off Water tank temperature Code 3021 Code 3022 3023 Offset temperature of DHW s thermo on Only Hydro Unit Not Hydro Unit HT Temp...

Page 26: ...ing Cooling DHW when Outing function is on 5011 Value of cooling leaving water temperature setting when Outing function is on 5012 Value of cooling indoor s room temperature setting when Outing function is on 5013 Value of heating leaving water temperature setting when Outing function is on 5014 Value of heating indoor s room temperature setting when Outing function is on 5017 Value ofWater Law s ...

Page 27: ...e button to enter the sub menu checking screen f f Using the buttons select a sub menu number and press the button to enter data checking screen f f When you enter the checking stage the current setting value will be displayed f f Press the button to move previous setting value f f While configuring the sub manu setting press the ESC button to exit to normal menu While configuring the checking pre...

Page 28: ...nstallation service mode 2 When using the self test mode of the wired remote controller press the and buttons for more than 3 seconds 3 You can operate the self test mode as follows f f Load list When pressing the corresponding button you can set the load On or Off Enter button Operating part LCD display Water pump Booster heater DHW valve 2 way valve DVM HT_HE RC EU_IM_EN_DB68 03973A 06 indd 28 2...

Page 29: ...t you don t press the Timer button for 5 seconds the previous status will be shown f f For the sensor fault or absence of sensor installation corresponding sensor temperature will be displayed as Er f f When you press the button that does not have a function will blink for 3 seconds f f When pressing the Delete button one time all the loads will be Off f f When all the loads are OFF status Cancel ...

Page 30: ...DVM HT_HE RC EU_IM_EN_DB68 03973A 06 indd 30 2017 05 25 오후 4 18 34 ...