Drain pipe and Drain Hose Installation

Care must be taken when installing the drainpipe and drain hose 

for the indoor unit so that condensate water is drained correctly 

outside. 

Fix the flexible hose to the drainpipe. 

 

The connection port of the flexible hose and PVC drainpipe must be   

       fixed with PVC adhesives. 

 

Check out that the connected part doesn’t leak.

1

Connect the flexible hose to the flexible hose port. 

 

  Make sure that a rubber ring is installed on the drain hose port.

 

2

Install the drainpipe as shortly as possible. 

 

 Give a slightly slant to the drainpipe for proper drainage of condensate 

water. 

 

There must be no gap on the connected part so that the drainpipe is 

       not separated from the flexible hose .

3

Insulate the drainpipe, and then fix it as indicated.

4

CAUTION

Install air ventilation to drain condensate water 
smoothly

.

Check that the indoor unit is level with the ceiling by using the leveler.

Air ventilation

Ceiling

Do not give the hose and upward gradient 
after the connection port. 
This will cause water to flow backwards when 
the unit is stopped, resulting in water leaks.

Do not apply force to the piping on the unit side when 
connecting the drain hose. The hose should not be 
allowed to hang loose from its connection to the unit. 
Fasten the hose to a wall, frame or other support as  
close to the unit as possible.

Support pieces

1~1.5m

1/100 or more

Upward gradient

Ceiling

Ceiling

If it is necessary to increase the height of the drain pipe, 
install the drainpipe straightly within 300 mm from the 
flexible hose port. If it is raised higher than 550 mm,there 
can be water leaks.

300mm or less

1/100 or more

Flexible hose

Band joint

Ceiling

55

0m

m

 o

r l

es

s

20mm or more

Drain hose 

port

Insulation drainpipe

Band

Band

Flexible 

hose

Drain 

hose 

port

Drain hose

Adhesives

Insulation cover band

Insulation cover drain

Band(Not supplied)

Indoor 

Unit

Drainpipe

Flexible hose

Summary of Contents for CH EAMC Series

Page 1: ...ENGLISH System Air Conditioner Cooling and Heating E S F I P D G R DB98 26330A 4 CH EAM 1 C Series ENGLISH ESPA OL FRAN AIS ITALIANO PORTUGU S DEUTSCH E HNIKA RUSSIAN INSTALLATION MANUAL...

Page 2: ...s outside impacts and so on Installing the unit If the power cord of this air conditioner is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order t...

Page 3: ...Connecting the Refrigerant Pipe 9 Cutting Flaring the Pipes 10 Performing Leak Test Insulation 11 Connecting the Cables to the Outdoor Unit 11 Drainpipe and Drain Hose Installation 12 Connecting the C...

Page 4: ...aline air Machine oil Sulphide gas Special environmental conditions If you must install the unit in such conditions first consult your dealer Accessories The following accessories are supplied with th...

Page 5: ...indoor unit on a ceiling that can support its weight Maintain sufficient clearance around the indoor unit Make sure that the water dripping from the drain hose runs away correctly and safely The indo...

Page 6: ...e 6 Air suction grille 950 0 5 9 242 4 4 3 8 1 2 1 4 6 6 1 4 6 0 6 1 322 246 305 0 9 1 840 57 57 8 0 2 7 5 4 1 4 8 9 2 0 0 2 322 242 246 305 4 6 0 6 1 0 9 1 840 0 1 3 0 3 2 0 0 1 0 8 260 25 25 290 57...

Page 7: ...bles and install the front panel Ensure that the ceiling is strong enough to support the weight of the indoor unit Before hanging the unit test the strength of each attached suspension bolt If the len...

Page 8: ...piping Note On delivery the indoor unit is loaded with refrigerant gas All this gas must therefore be purged before connecting the assembly piping To purge the inert gas proceed as follows Unscrew th...

Page 9: ...refrigerant pipe to protect the condensate water on the outside of pipe falling onto the floor and the efficiency of the unit will be better 2 Cut off any excess foam insulation 3 Be sure that there m...

Page 10: ...ipe and modify the flare 4 Check that the flaring is correct referring to the illustrations below for examples of incorrect flaring 5 Align the pipes and tighten the flare nuts first manually and then...

Page 11: ...tightly against body without any gap No gap NBR T13 0 or thicker Connecting the Cables to the Outdoor Unit Two electric cables must be connected to the outdoor unit The connection cord connecting the...

Page 12: ...that the indoor unit is level with the ceiling by using the leveler Air ventilation Ceiling Do not give the hose and upward gradient after the connection port This will cause water to flow backwards...

Page 13: ...onfirm that the water flows out through the drain hose 3 Reassemble the cover drain pump 4 You can check the drainage only when the air conditioner is in cool mode Note If you do not pour water inside...

Page 14: ...h the ceiling the hole on the wall 3 Reassemble the electrical component box cover carefully tightening the screw 4 Wiring Diagram Note 1 Connect the Connection Cord as seen in picture and the torque...

Page 15: ...ntralized controller 4 If you install optional accessories such as the wired remote controller cen tralized controller etc see an appropriate installation manual 5 If an optional accessory is not inst...

Page 16: ...component box cover For your safety you must install the safety net For details about installing the panel refer to the manual for the panel Fix the safety net to the electric component cover box wit...

Page 17: ...ture sensor Error of the condensor temperature sensor Error of the discharge temperature sensor 1 No communication for 2 minutes between indoor units Communication error for more than 2 minutes 2 Indo...

Page 18: ...perature discharge 5 Error of reverse phase 6 Compressor down due to 6 th detection of freezing X LED Display On Flickering X Off If you turn off the air conditioner when the LED is flickering the LED...

Page 19: ...ure sensor Open Short Error of condensor temperature sensor Open Short Error of discharge temperature sensor Open Short System down caused by communication error after completion of tracking Mismatchi...

Page 20: ...e joint 1 Owner s instructions 1 Installation manual 1 Wireless Remote Controller Accessories Wireless remote controller 1 Battery 2 Remote control holder 1 STS 2S 2x10 tapped screw 2 Owner s instruct...

Page 21: ...Scheduler Accessories Cable tie 2 Cable clamp 2 M4x16 tapped screw 4 Owner s instructions 1 Installation manual 1 7 day Scheduler 1 Transmitter Accessories Transmitter power cable 1 Transmitter commun...

Page 22: ...E 22 MEMO...

Page 23: ...ENGLISH E 23...

Page 24: ......

Reviews: