background image

5. Troubleshooting

5-1 Troubleshooting Method and Precautions

5-1-1 Checking of power source

5-1-2 Check the parts that be weak or fragile

5-1-3 Check the terminals for proper connection

5-1-4 Refer to the table below when there is any malfunction;

Samsung Electronics

5-1

Check to see whether the voltage of the power source is 220 ~ 240V, 50Hz.
The air conditioner may not operate properly if the voltage is out of this range.

Procedures

1

Check to see whether the electric circuit or electric parts are damaged before repairing the air conditioner.

2

Conduct the following generally to check whether the electric circuit or other electric parts are damaged.

No

Trouble

Checkpoints

Possible cause

The compressor 
does not operate.

The motor does 
not operate.

The cooling capacity 
is low.

The heating capacity 
is low

Noise

1. Check the position of the thermostat.
2. Check the position of the select switch.
3. Check the connection of the lead wire.
4. check the overload protector.
5. Check the compressor.

1. Check the connection of the lead wire

and switch.

2. Check the motor.
3. Check whether the unit is deicing.

1. Check the refrigerant for leak.
2. Check the evaporator condition.

(freezing, clogging with dust, etc.)

❊ 

The temperature difference between
the air inlet side and air outlet side
should be 12°C at the minimum.

❊ 

Standard state
Indoor : 27°C, Outdoor : 35°C

1. Check the refrigerant for leak.
2. Check the evaporator condition.

(freezing, clogging with dust, etc.)

3. Check whether the drain equipment

(DRAIN PAN, DRAIN TUBE) is installed.

❊ 

The temperature difference between
the air inlet side and outlet side 
should be 12°C at the minimum.

❊ 

Standard state
Indoor : 20°C, Outdoor : 7°C

❊ 

Adequate operating temperature
• Heating : Indoor : 0°C~21°C approx.

Outdoor : 28°C or less.

1. Check the vibration of the pipe.
2. Check the propeller fan and blower for 

looseness and weakness.

3. Check the motor bearing for noise.
4. Compare the compressor noise with

other compressors.

1. The setting temperature is higher than the

room temperature in cool mode.

2. The setting temperature is lower than the

room temperature in heat mode.

3. Lead wire disconnected.
4. O.L.P. damaged.
5. Compressor damaged.

1. Lead wire disconnected.
2. Switch damaged.
3. Motor damaged.
4. The unit is operating on the deice mode.

1. The leak is caused by a pipe crack.
2. Shortage of the refrigerant.
3. Clean the evaporator, and air filter.

1. The leak is caused by a pipe crack.
2. Shortage of the refrigerant.
3. Clean the evaporator, and air filter.
4. Install the drain pan and drain plug.

1. The pipe is in contact with other parts.
2. The tightening of the hexagon nut is faulty.
3. Damage of the motor.
4. Damage of the compressor.

Summary of Contents for AWH120JE

Page 1: ...TIONER CONTENTS 1 Precautions 2 Product Specifications 3 Installation and Operating Instructions 4 Disassembly and Reassembly 5 Troubleshooting 6 Exploded Views and Parts List 7 Block Diagram 8 Wiring Diagram SERVICE Manual THERM OSTAT OPERA TION ...

Page 2: ...ELECTRONICS Samsung Electronics Co Ltd MAR 1998 Printed in Korea Code No DB81 10151A 1 ...

Page 3: ... cord and avoid tapping into a power cord This practice may result in malfunction or fire 6 After completing repairs and reassembly check the insulation resistance Procedure Prior to applying power measure the resistance between the power cord and the ground terminal The resistance must be greater than 30 megohms 7 Make sure that the grounds are adequate 8 Make sure that the installation condition...

Page 4: ...rator Fan Fan Motor Compressor Rotary Overload Protect Compressor Capacitor Fan Motor Capacitor Fan Speed Control Thermo Control Unit of Measure mm mm Volt Hz A W FREON g BTU h BTU h W kg Row Type Row Type W Model µF VAC µF VAC AWH120JE 123JE COOL HEAT Window 600 X 394 X 555 699 X 441 X 638 220 240 Single 50 5 9 5 3 1 350 1 210 R 22 680 11 500 11 500 8 5 9 5 45 2 X 14 Propeller Fan 2 X 14 Blower A...

Page 5: ...2 2 Dimensions 2 2 1 Main Unit 2 2 Samsung Electronics 600 395 395 595 Front view Side view Unit mm ...

Page 6: ...e difference between the air inlet side and air outlet side should be 12 C at the minimum Standard state Indoor 27 C Outdoor 35 C 1 Check the refrigerant for leak 2 Check the evaporator condition freezing clogging with dust etc 3 Check whether the drain equipment DRAIN PAN DRAIN TUBE is installed The temperature difference between the air inlet side and outlet side should be 12 C at the minimum St...

Page 7: ...6 Exploded View and Parts List 6 1 Main unit 6 1 Samsung Electronics 26 27 1 8 9 17 12 15 16 2 3 4 5 13 11 14 4 3 2 1 5 6 7 14 15 19 17 18 16 13 9 8 10 11 12 20 22 21 25 23 24 28 10 6 7 ...

Page 8: ...1 1 12 DB90 50142A ASSY FRAME UP AWH120JE 1 1 13 DB96 30272A ASSY COND AWH120JE 1 1 14 DB63 10355A CAP DRAIN CR 1 1 15 DB90 20198A ASSY BASE AWH120JE 48F 1 1 16 DB27 10030B SOLENOID COIL ASS Y AWH090ZE 1 1 17 DB62 31722A TUBE CAPILLARY ASS Y ID 1 7 L1300 1 1 18 DB96 10591A ASSY TUB 4 WAY V V ASS Y 1 1 19 DB95 10062A ASS Y COMP 48H124JV1E4 1 1 20 DB72 50585A CLOTHE SOUND T35 1 1 21 DB60 30028A NUT ...

Page 9: ...Samsung Electronics 6 2 Ass y Control 6 3 1 7 8 16 11 14 15 2 3 4 12 10 13 9 5 6 ...

Page 10: ... 5 2501 001124 C OIL 3 5 30µF 450VAC 1 1 6 DB65 10100A CLIP CAPACITOR SECC P TO 8 1 1 7 DB95 20065F SWING MOTOR M2LJ49ZU32 1 1 8 DB47 20065A THERMOSTAT DEICE 3Pin 1 1 9 DB45 10009A TIMER DEFROST D2506 50Min 1 1 10 DB47 20060A THERMOSTAT BUA 129 1 1 11 DB34 90085A SELECTOR SWITCH 5PIN 7STEP 1 1 12 DB64 70081A PANEL CONTROL M HIPS 1 1 13 DB64 40169A INLAY CONTROL M AWH120JE 1 1 14 DB64 50138A KNOB T...

Page 11: ...BRN SEESAW S W YEL RED SELECTOR S M PLUG GRN YEL GROUND BRN CAPACITOR DUAL RED BLU ORG RED GRN YEL RED BLK RED RED BLU YEL ORG GRN BLU RED GRN SKY BLU RED RED BLU BLU BLY THERMOSTAT DEICE DEICE TIMER SOLENOID COIL GRN 1 2 1 2 3 5 4 4 3 8 6 4 2 1 GRN YEL F M BLK WHT RED S C O L P BLK COMP THERMOSTAT BLU YEL RED BLU YEL ORG RED WHT YEL ORG BRN S L H M GRN 1 3 2 R ...

Reviews: