Samsung Electronics
7-2
7-2 Refrigerating Cycle Block Diagram
Refrigerating cycle temperature and pressur e
INDOOR UNIT
OUTDOOR UNIT
Heat
exchanger
(Evaporator)
Gas side
3-way valve
2-way valve
Liquid side
Capillary tube
Cooling
Gas leak check point
Heat
exchanger
(Condenser)
Heating
Capillary tube
Check valve
Compressor
4-way valve
T
T
STD Pressure
Piping Temp.
UseTemp. Condition (°C)
Operating Condition
(kg/cm2G)
T1
T2
Indoor
Outdoor
3-WAY V/V
DB
WB
DB
WB
Standard
4.0~5.0
10~12
10~12
27
19(19.5)
35
24
Cooling
Max over load
-
16~18
14~18
29
19
54
24
Low temp
-
1~4
1~4
21
16
21
16
Standard
19~23
32~36
60~70
20(21)
-
7
6
Heating
Max over load
-
36~40
65~75
27
-
21
16
Deice
-
28~32
40~45
20
-
2
1