10-2-11 Compressor starting error
Indoor display
3-LED DISPLAY
7-SEG DISPLAY
DESCRIPTION
LED1
LED2
LED3
E461
Comp starting error
Outdoor display
Comp starting error
LED ON
LED BLINKING
LED OFF
1. Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
Download the EEPROM data
Exchange the compressor
Is the restart error occurred again?
Is the connection of compressor wire is normal?
Is the restart error occurred again?
Is the compressor body and interphase
resistance insulated?
NO
NO
NO
NO
Terminate the service
Connect the comp wire normally
Terminate the service
Exchange the Outdoor PBA
YES
YES
YES
YES
Summary of Contents for AR18NSFHBWKNEU
Page 11: ......
Page 12: ......
Page 17: ......
Page 24: ...4 10 s c i n o r t c e l E g n u s m a S 2 2 ...
Page 41: ...DB68 05092A 4 ...
Page 42: ...7 2 _18K DB68 06674A 1 ...
Page 43: ...7 3 7 2 Outdoor Unit_24K DB68 06675A DB68 06675A 00 ...
Page 45: ...S a m s u n g C o n f i d e n t i a l S a m s u n g ...
Page 46: ...8 3 8 3 Refrigerating Cycle Diagram ...
Page 53: ...9 1 2 9 2 AR18NSFPEWQXEU AR24NSFPEWQXEU AR18NSFHBWKXEU AR24NSFHBWKXEU Outdoor Unit ...
Page 90: ...10 3 10 36 ...
Page 91: ......
Page 92: ......
Page 95: ...12 3 12 3 ...
Page 96: ...12 4 12 4 ...
Page 97: ...12 5 ...
Page 98: ...12 6 ...
Page 100: ...12 5 2 12 8 ...
Page 101: ...12 6 12 9 12 6 1 12 6 2 ...
Page 102: ...12 7 12 7 1 12 10 ...
Page 103: ...12 7 2 12 11 ...
Page 105: ......