53
10-2-5 Outdoor Cond temperature sensor error
Indoor display
7-SEG DISPLAY
DESCRIPTION
C231
Outdoor Cond temperature sensor error
Outdoor display
Outdoor Cond temperature sensor error
LED ON
LED BLINKING
LED OFF
1. Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
2. Troubleshooting procedure
Model
“A”
“B”
ALL
CN251
CN251 #5-#6
YES
YES
NO
NO
NO
YES
YES
Is the sensor connector("A")
connected correctly in accordance
with a color?
Is the sensor resistance value
"B" 10kohm±3% at the room temperature
of 25
℃ ?
Connect the sensor to PBA connector supply
power and measure the voltage of “B”
communication cable
Reconnect the sensor connector.
Sensor Replace
Sensor resistance value : 20 - 12.09kohm
30 - 8.31kohm
35 - 6.94kohm
40 - 5.83kohm
Exchange the Outdoor PBA
Below 0.5Vdc or Over 4.5Vdc?
Micom error or connector check
Exchange the Outdoor PBA
Summary of Contents for AR09TXFYAWKNEU
Page 43: ...43 8 3 DISPLAY PCB DB92 04833B ...
Page 68: ...68 11 1 Indoorunit 11 Block Diagram ...
Page 69: ...69 11 2 Outdoorunit ...