11. Installation

Installation of the product

 •

Our units must be installed in compliance with the spaces indicated in the installation manual to ensure either accessibility from 

both sides or ability to perform routine maintenance and repairs. The units’ components must be accessible and that can be 

disassembled in conditions of complete safety either for people or things. For this reason, where it is not observed as indicated into 

the Installation Manual, the cost necessary to reach and repair the unit (in safety, as required by current regulations in force) with 

slings, trucks, scaffolding or any other means of elevation won’t be considered in-warranty and will be charged to end user.

 •

The outdoor unit shall be installed in an open space that is always ventilated.

 •

The local gas regulations shall be observed.

 •

To handle, purge, and dispose the refrigerant, or break into the refrigerant circuit, the worker should have a certificate from an 

industry-accredited authority.

 •

The installation of pipings shall be kept to a minimum.

 •

Do not install the indoor unit in the following areas:

 -

Area filled with minerals, splashed oil, or steam. It will deteriorate plastic parts, causing failure or leakage.

 - Area that is close to heat sources.
 -

Area that produces substances such as sulfuric gas, chlorine gas, acid, and alkali. It may cause corrosion of the pipings and brazed joints.

 -

Area that can cause leakage of combustible gas and suspension of carbon fibers, flammable dust, or volatile flammables.

 -

Area where refrigerant leaks and settles.

 -

Area where animals may urinate on the product. Ammonia may be generated.

 •

Do not use the indoor unit for preservation of food items, plants, equipment, and art works. This may cause deterioration of their quality.

 •

Do not install the indoor unit if it has any drainage problem.

 •

For the multi system, this indoor unit can be conncected to an R-32 or R-410A outdoor unit.  Check the type of refrigerant in the 

outdoor unit.

 •

Because your air conditioner contains R-32 refrigerant, make sure that it is installed, operated, and stored it in a room whose

floor area is larger than the minimum required floor area specified in the following table:

Wall-mounted type

m (kg)

A (m²)

≤ 1.842

No requirement

1.843

4.45

1.9

4.58

2.0 

4.83 

2.2 

5.31 

2.4 

5.79 

2.6 

6.39 

2.8 

7.41 

3.0 

8.51 

 -

m : Total refrigerant charge in the system

 -

A : Minimum required floor area

 •

IMPORTANT: it’s mandatory to consider either the table above or taking into consideration the local law regarding the

minimum living space of the premises.

 •

Minimum installation height of indoor unit is 0.6 m for floor mounted, 1.8 m for wall, 2.2 m for ceiling.

 •

The actual refrigerant charge shall be in accordance with the room size within which the refrigerant containing parts are

installed.

 •

The ventilation machinery and outlets shall be operating adequately and not obstructed.

 •

If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant.

 •

Marking to the equipment shall continue to be visible and legible. Markings and signs that are illegible shall be corrected.

 •

Refrigerating pipe or components shall be installed in a position where they are unlikely to be exposed to any substance

which may corrode refrigerant containing components, unless the components are constructed of materials which are

inherently resistant to being corroded or are suitably protected against being so corroded.

11. Installation

Summary of Contents for AR TX AWKNEU Series

Page 1: ...Installation RAC forEurope INV R32 50Hz HP Model AR TX AWKNEU Indoor Unit AR TX AWKXEU Outdoor Unit ...

Page 2: ...urope AR7500 19 10 29 Ver 2 0 Released AR9500T RAC new line up TDB AR4500 AR5500 AR9500 19 11 21 Ver 3 0 Released AR9500T RAC new line up TDB AR4500 AR5500 AR7500 AR9500 19 12 13 Ver 3 1 Updated some specification data 20 02 06 Ver 3 2 Updated the Sound data of Outdoor Unit 20 11 25 ...

Page 3: ...eristics C Motion Detect Sensor Wi Fi Tri care Filter E Wi Fi Tri care Filter F Wi Fi H 6 Design Segment A Wind Free GEO C Wind Free AIRISE Y GEO Z AIRISE 7 Version A Z 1 digit 8 Color WK DA White 9 Set N Indoor Unit X Outdoor Unit Set Nomenclature Model Name AR 1 09 2 T 3 X 4 F 5 C 6 A 7 WK 8 N 9 EU Buyer ...

Page 4: ...orUnit Model Type Design Image AR9500 Wind Free GEO AR7500 Wind Free AIRISE AR5500 GEO AR4500 AIRISE Model Type Design Capacity kW 2 5 3 5 5 0 6 5 AR9500 Wind Free GEO AR7500 Wind Free AIRISE AR5500 GEO AR4500 AIRISE ...

Page 5: ...5 Model Type Design Capacity kW 2 5 3 5 5 0 6 5 AR9500 Wind Free GEO AR7500 Wind Free AIRISE AR5500 GEO AR4500 AIRISE Line up OutdoorUnit ...

Page 6: ... 6 Contents 11 Installation 85 ...

Page 7: ...and settles Areawhere animals mayurinate on the product Ammonia maybe generated Do not usethe indoorunitforpreservation offood items plants equipment and artworks This maycause deterioration oftheirquality Do not install the indoorunit if it has anydrainage problem Forthe multi system this indoorunit can be conncected to an R 32 orR 410Aoutdoorunit Check the type of refrigerant in the outdoorunit ...

Page 8: ...ectric and drain Compressor condenser outdoor Unit m Model Pipe length Pipe height Minimum Maximum Standard forfactory charge Maximum 07 09 12 3 15 5 8 18 24 3 30 5 15 CAUTION Outdoor Unit Outerwall Indoor Unit Cut insulation to have rainwater drained Make a U trap A on the pipe which is connected to the indoor unit at outerwall and cut the bottom part of the insulation about 10 mm to prevent rain...

Page 9: ...bed in this manual that are not expressly approved by the manufacturer could void the manufacturer s warranty To determine where to locate the indoor and outdoor units you must survey the entire site and consider many variables The goal is to select locations that comply with all safety precautions while also minimizing the total effort involved Indoorunit location requirements WARNING Do not inst...

Page 10: ...ting the weight of both the L bracket and the outdoor unit If the unit falls it may result in crushing electric shock fire or explosion that could cause death severe personal injury or property damage Installation Guide at the seashore Make sure to follow below guides when installing at the seashore 1 Do not install the product in a place where it is directly exposed to sea water and sea breeze Ma...

Page 11: ...at can block the sea breeze and the height and width of the wall should be 1 5 times larger than the size of the outdoor unit You must secure more than 700 mm of space between the protection wall and the outdoor unit for air circulation Minimum clearances forthe outdoorunit Legends Wall Minimum clearance in mm 600 300 Airflow direction Top view Side view Examples forinstalling one outdoorunit Unit...

Page 12: ...upplied mounting screws and anchors if applicable attach the bracket to the wall Screw Location x 4ea Level Drilling the wall penetration 1 Determine the position of the hole through which the piping bundle consisting of power and communication cables refrigerant pipes and the drain hose will pass Consider the following The hole inner diameter must be 65 mm The recommended hole location is behind ...

Page 13: ... with the outdoor unit WARNING Do not modify the power cable in any way Doing so may cause electric shock or fire due to poor connection poor insulation or current limit override Make sure to comply with the technical standards of electrical installations and the wiring regulations in the local area This appliance must be properly grounded Do not ground the appliance to a gas pipe plastic water pi...

Page 14: ... uses the R 32 refrigerant be cautious not to generate a spark bykeeping the following requirements Do not remove the fuseswith poweron Do not disconnect the powerplug from thewall outlet with poweron It is recommended to locate the outlet in a high position Place the cords so that theyare not tangled 2 Tighten the terminal block screw L1 L2 F1 F2 3 In Step 2 2 step 3 you determined the exit posit...

Page 15: ... the outdoor unit and the ground for installation Ensure that the drained water runs off correctly and safely Allow enough separation distance between the product and the ground 80 mm Estimated snow fall Snow proof hood Ground On the ground 1 Place the outdoor unit in the selected installation location Step 1 1 on page 93 ensuring proper clearances and with the arrow on top of the unit pointing aw...

Page 16: ...odes Adding refrigerant if needed The outdoor unit is charged with sufficient R 32 refrigerant to support up to a 5 m line set For lengths greater than 5 m you must add 15 g of refrigerant per meter of additional length after the lines are evacuated 1 Calculate the additional refrigerant required Additional grams of R 32 Total line set meter 5 15 2 Connect the common hose of the manifold gauge set...

Page 17: ... this manual the factory refrigerant charge of the product the additional refrigerant amount charged in the field and the total refrigerant charge on the refrigerant charge label supplied with the product Refrigerant type GWP value R 32 675 GWP Global Warming Potential Calculating tCO e kg x GWP 1000 Indoor unit Outdoor unit Unit Kg tCO e a b c NOTE Factory refrigerant charge of the product see un...

Page 18: ...Head Office Suwon Korea 129 Samsung Ro Yeongtong Gu Suwon City Gyeonggi Do Korea 16677 Website www samsung com https partnerhub samsung com Email airconditioner samsung com Images and data in this book may subject to change without prior notice ...

Reviews: