24
English
Installation
•
the additional refrigerant amount charged
in the field and
•
+ the total refrigerant charge. on the
refrigerant charge label supplied with the
product.
Refrigerant type
GWP value
R-32
675
• GWP=Global Warming Potential
• Calculating tCO
2
e : kg x GWP / 1000
Unit
Kg
tCO
2
e
①
, a
②
, b
①+②
, c
NOTE
a Factory refrigerant charge of the product: see
unit name plate
b Additional refrigerant amount charged in the
field (Refer to the above information for the
quantity of refrigerant replenishment.)
C Total refrigerant charge
d Refrigerant cylinder and manifold for charging
CAUTION
•
The filled-out label must be adhered in the
proximity of the product charging port (e.g. onto
the inside of the stop valve cover).
•
Make sure that the total refrigerant charge does
not exceed
(A)
, the maximum refrigerant charge,
which is calculated in the following formula:
Maximum refrigerant charge
(A)
= factory
refrigerant charge
(B)
+ maximum additional
refrigerant charge due to piping extension
(C)
(Unit : g)
Model
A
B
C
**09MX*****
**12MX*****
1070
920
150
**09NX**B**
**12NX**B**
900
750
150
**09NXWXC**
**12NXWXC**
850
700
150
**09NXCX***
**12NXCX***
1000
850
150
Indoor unit
Outdoor unit