1. Combination Table
NOTE
•Make sure to use an indoor unit that is compatible with DVM S.
•Indoor units can be connected within the range indicated in following table.
•If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
•Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 × Σ( Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ( Outdoor unit capacity)
※
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be
assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
※ Maximum 32 Wall-mount type indoor units with EEV (AM∗∗∗∗NQDEH∗∗∗, AM∗∗∗JNVDKH∗∗∗) can be connected.
Essential
Capa
Model Name
Number of
individual outdoor units
10
12
14
16
18
10HP
AM100AXVDGH/EU
1
1
12HP
AM120AXVDGH/EU
1
1
14HP
AM140AXVDGH/EU
1
1
16HP
AM160AXVDGH/EU
1
1
18HP
AM180AXVDGH/EU
1
1
20HP
AM200AXVDGH1EU
2
22HP
AM220AXVDGH1EU
1
1
24HP
AM240AXVDGH1EU
1
1
26HP
AM260AXVDGH1EU
1
1
28HP
AM280AXVDGH1EU
2
1
1
30HP
AM300AXVDGH1EU
2
1
1
32HP
AM320AXVDGH1EU
2
2
34HP
AM340AXVDGH1EU
2
1
1
36HP
AM360AXVDGH1EU
2
2
38HP
AM380AXVDGH1EU
3
1
1
1
40HP
AM400AXVDGH1EU
3
1
1
1
System Model
Capacity (HP)
2
2
2
2