2-8
Samsung Electronics
Outdoor Unit(Continue)
TYPE
DVM S HR - 208-230V
Model
AM072FXVAFR/AA
AM096FXVAFR/AA
AM120FXVAFR/AA
AM144FXVAFR/AA
Mode
HR
HR
HR
HR
Power
Ø,V,Hz
3/208-230/60
3/208-230/60
3/208-230/60
3/208-230/60
Capacity
Cooling (Nominal)
Btu/h
72,000
96,000
120,000
144,000
Cooling (Rated)
Btu/h
69,000
92,000
114,000
138,000
Heating (Nominal)
Btu/h
81,000
108,000
135,000
162,000
Heating (Rated)
Btu/h
77,000
103,000
129,000
154,000
Power Consumption
(Nonducted, AHRI)
Cooling
W
5,350
6,680
9,140
12,340
Heating
W
5,430
7,130
9,520
12,400
Current consumption
(Nonducted, AHRI)
Cooling
A
14.6 18.2 24.9 33.7
Heating
A
14.8 19.5 26.0 33.8
EER
(Nonducted, AHRI)
Cooling
Btu/Wh
12.9 13.8 12.5 11.2
Heating
W/W
4.15 4.23 3.97 3.64
IEER(AHRI)
Cooling
W/W
23.0 26.0 24.2 22.7
Compressor
Model
-
DS-GB052FBVASG
DS-GB052FBVASG
DS-GB052FBVASG
DS-GB052FBVASG
Output
kW
33.1
33.1 33.1 33.1
Excluded Volume
cc/rev
52.0
52.0
52.0
52.0
Capacity
Btu/h
58,000
58,000
58,000
58,000
Quantity
EA
1 2 2 2
Lubricant oil
OIL
Liter
FV68D(PVE)
FV68D(PVE)
FV68D(PVE)
FV68D(PVE)
Factory
Charging
Liter
3.9 6.2 6.2 6.2
Refrigerant
Type
-
R410A
R410A
R410A
R410A
Factory Charging
lb
12.13
16.31
16.31
19.18
FAN
Ø
mm
700
575
575
575
MAX STEP
-
19
29
29
31
CODE
-
DB31-00298A
DB94-03285C
DB94-03285C
DB94-03285C
MAX RPM
STEP(RPM)
800
1050
1050
1100
Quantity
EA
1
2
2
2
CMM
205
260
260
270
Piping
Connections
Gas
Inch
3/4"(19.05)
7/8"(22.22)
1+1/8"(28.58)
1+1/8"(28.58)
Dis. Gas
Inch
5/8"(15.88)
3/4"(19.05)
7/8"(22.22)
7/8"(22.22)
Liquid
Inch
3/8"(9.52)
3/8"(9.52)
1/2"(12.7)
1/2"(12.7)
DIMENSION
NET
mm
880x1695x765
1295x1695x765
1295x1695x765
1295x1695x765
GROSS
mm
948x1912x832
1363x1912x832
1363x1912x832
1363x1912x832
NET
kg
195
284
284
299
GROSS
kg
211
303
303
318
Operating Temp.
Range
Cooling
ሥ
23~118
23~118
23~118
23~118
Heating
ሥ
-4~75
-4~75
-4~75
-4~75
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 80.6
ሥ
DB/66.2
ሥ
WB, outdoor 95
ሥ
DB, length 50m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 68
ሥ
DB, outdoor 44.6
ሥ
DB, length 50m of piping, fall 0ft standard.
2. If proper form heating capacity is outdoor temperature 44.6
ሥ
standard and outdoor temperature goes down by below zero,
heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 656ft (Equivalent length 722ft).
5. If the indoor unit is below, height length allows up to 361ft (If over 164ft, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 131ft.