4-4-36 MCU branch part setup error – Set as being used without connection to an Indoor unit
1. How to check
Adjust the Dip switch that sets up the use of MCU branch part to ‘Not-Used'. After completing resetting, press the outdoor unit's
K3 button to reset or turn off to restart.
MCU BOX #0
MCU PCB
OFF
MCU
address setup
ON
Indoor unit address
Branch part use setup
4
2
2
0
5
6
0
Branch A
B
C
D
E
F
MCU BOX #1
MCU PCB
OFF
MCU
address setup
ON
Indoor unit address
Branch part use setup
4
0
1
2
5
7
1
Branch A
B
C
D
E
F
MCU BOX #1
MCU PCB
OFF
ON
1
3
7
9
0
0
1
Branch A
B
C
D
E
0
F
MCU BOX #1
MCU PCB
OFF
MCU address setup
ON
Indoor unit
Indoor unit address
Branch part use setup
4
4
2
1
5
6
0
Branch A
4
B
C
D
E
5
F
6
2
Outdoor unit display
Indoor unit display
Operation
Timer
Criteria
• Occurs when MCU PIPE is set as being used, yet not connected to an indoor unit
Cause of problem
• Pipe is not installed to the indoor unit with assigned address on MCU