Troubleshooting
Samsung Electronics
4-17
Installation options for the 02 series
• Even if you set the Use of drain pump (SEG8) option to 0, it is automatically set to 2 (the drain pump is used with 3 minute
delay).
• If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to 2 (1000
hours).
• If you set an option to a value that is out of range specified above, the option is automatically set to 0 by default.
• The SEG5 option (Use of central control) is set to 1 (Use) by default. Therefore, you don't need to set the SEG5 option
additionally. Note that even if the central control system is not connected, no errors occur. If you want a specific indoor
unit not to be controlled by the central control system, set the SEG option of that indoor unit to 0 (Disuse).
• The external output of SEG15 is generated via MIM-B14 connection. (Refer to the manual of MIM-B14.)
• If you set the Individual control with remote control (SEG20) option to a value other than 0 to 4, it is automatically set to 0
(Indoor 1).