9
English
Instal
lation
This appliance is approved for zero (0) inches clearance to combustible material on any part of the air handler exterior
casing and the inlet or outlet ducts providing NO electric heater is being used. There is a one (1) inch clearance on the
supply plenum and supply air duct when an electric heater is installed in the appliance. Refer to Table below for clearance
to combustibles information.
Top (inches)
Back (inches)
Sides (inches)
Front of unit
Duct (inches)
Alcove (inches)
Closet (inches)
0
0
0
30
6
1 *
* when electric heat kit accessory is installed
Return air requirements
0"
0"
Return Air Requirements
In order for the air handler to work properly, a closet or alcove must have a certain total free area opening for the return air.
For A/C and HP Air Handlers 1/3 HP Blower Motor
Minimum 200 in² free area opening
• Use Return Grille that can supply sufficient air to ensure proper performance.
For A/C and HP Air Handlers 1/2 HP Blower Motors
•
Minimum 250 in² free area opening
• Use Return Grille that can supply sufficient air to ensure proper performance.
For A/C and HP Air Handlers with Electric Heat use 3/4 HP Blower Motor
•
Minimum 390 in² free area opening
• Use Return Grille that can supply sufficient air to ensure proper performance.
For A/C and HP Air Handlers use 1.0 HP Blower Motor)
•
Minimum 430 in² free area opening
•
Use Return Grille with a minimum 430 in² free area opening
The return air opening can be located in the floor, on a closet front door or in a side wall above the air handler casing. If
opening for the return air is located in the floor, side walls, or closet door anywhere below the appliance casing, a 6 inch
minimum clearance between the appliance and the wall or door must be provided on the side where the return is located
to provide for proper air flow. The 6 inch minimum clearance is not required if there is a return grille installed above the
appliance casing, providing the grille has a sufficient return air opening.
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 9
2020-02-14 오전 10:33:30
Summary of Contents for AM0 SERIES
Page 45: ...45 English Appendix Memo AM072TNZDCH_IM_DVM V AHU_AA_EN_ indd 45 2020 02 14 오전 10 33 41 ...
Page 46: ...AM072TNZDCH_IM_DVM V AHU_AA_EN_ indd 46 2020 02 14 오전 10 33 41 ...
Page 91: ...45 Français Annexe Note AM072TNZDCH_IM_DVM V AHU_AA_FR_ indd 45 2020 02 14 오전 10 35 49 ...
Page 92: ...AM072TNZDCH_IM_DVM V AHU_AA_FR_ indd 46 2020 02 14 오전 10 35 49 ...