background image

7

English

Ins
tallation Pr

oc

edur

e

Step 5  Connecting the refrigerant pipe

Connect indoor and outdoor units with field-supplied 
copper pipes by means of flare connections. Use insulated 
seamless refrigeration grade pipe only, (Cu DHP type 
according to ISO1337), degreased and deoxidized, suitable 
for operating pressures of at least 4200 kPa and for burst 
pressure of at least 20700 kPa. Under no circumstances 
must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

• 

The smaller one is for the liquid refrigerant

• 

The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You 
may need to extend the pipe using the assembly pipe. 
(optional) 
The connection procedure for the refrigerant pipe varies 
according to the exit position of the pipe when facing the 
wall:

• 

Right (A)

• 

Left (B)

• 

Underside (C)

• 

Rear

Right(B)

Left(A)

Underside(C)

Cut out the appropriate knock-out piece on the rear of 
the indoor unit unless you connect the pipe directly 
from the rear. 

Smooth the cut edges.

Remove the protection caps of the pipes and connect 
the assembly pipe to each pipe. Tighten the nuts first 
with your hands, and then with a torque wrench, 
applying the following torque: 

Torque 

wrench

Flare nut

Union

Spanner

Refrigerant oil

Outer diameter (mm)

Torque (N•m)

Torque (kgf•cm)

6.35

14~18

140~180

9.52

34~42

350~430

12.70

49~61

500~620

15.88

68~82

690~830

  NOTE

• 

If you want to shorten or extend pipes, refer to Step 6  
Cutting or flaring the pipes.

Cut off the remaining foam insulation.

If necessary, bend the pipe to fit along the bottom 
of the indoor unit. Then pull it out through the 
appropriate hole.

• 

The pipe should not project from the rear of the 
indoor unit.

• 

The bending radius should be 100 mm or more.

Pass the pipe through the hole in the wall.

For further details on how to connect to the outdoor 
unit and purge the air, refer to Step 4  Purging the unit.

  NOTE

• 

The pipe will be insulated and fixed permanently into 
position after finishing the installation and the gas leak 
test; refer to page 9 for further details.

• 

DO NOT WALL UP THE PIPE CONNECTION!

All refrigerant pipe connection must be easy accessible 
and serviceable.

DVM Boracay_IM_EN_DB68-06417A-00_16.09.22.indd   7

2016/9/22   11:29:11

Summary of Contents for AM KNTD Series

Page 1: ...DB68 06417A 00 DVM Boracay_IM_EN_DB68 06417A 00_16 09 22 indd 36 2016 9 22 11 29 08...

Page 2: ...AM KNTD AM KNQD Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference DVM Boracay_IM_EN_DB68 06417A 00_...

Page 3: ...Step 7 Performing leak test Step 8 Wrapping the pipes with the insulation Step 9 Installing the drain hose Step 10 Optional Changing direction of the drain hose Step 11 Connecting the power and commu...

Page 4: ...MSUNG s technical support if the unit produces smoke if the power cable is hot or damaged or if the unit is very noisy Always remember to inspect the unit electric connections refrigerant tubes and pr...

Page 5: ...power cable modification extension wiring and multiple wire connection It may cause electric shock or fire due to poor connection poor insulation or current limit override When extension wiring is re...

Page 6: ...rted or noise from being generated As far away as possible from fluorescent and incandescent lights so that the remote control can be operated well A place where the air filter can be replaced easily...

Page 7: ...ttention to the weight of the indoor unit NOTE If you mount the plate to a concrete wall by using plastic anchors make sure that gaps between the wall and the plate created by projected anchor are les...

Page 8: ...he cut edges 3 Remove the protection caps of the pipes and connect the assembly pipe to each pipe Tighten the nuts first with your hands and then with a torque wrench applying the following torque Tor...

Page 9: ...type Unit mm Outer diameter A Flare tool for R410A clutch type Conventional flare tool Clutch type Wing nut type 6 35 0 0 5 1 0 1 5 1 5 2 0 9 52 0 0 5 1 0 1 5 1 5 2 0 12 70 0 0 5 1 0 1 5 1 5 2 0 15 88...

Page 10: ...pipe hose and cables Then place the indoor unit on the installation plate 1 To avoid condensation problems place heat resistant poly ethylene foam separately around each refrigerant pipe in the lower...

Page 11: ...t use the other drain hose hole block it with a rubber stopper 4 Pass the drain hose under the refrigerant pipe keeping the drain hose tight 5 Pass the drain hose through the hole in the wall Check if...

Page 12: ...er cable 1 L 2 N by 100 mm 100mm 6 Connect the earth cable to the plate on the evaporator as like the following picture Power earth cable 7 Connect F3 F4 for communication wires at the back side of th...

Page 13: ...2 5 mm2 2 5 mm2 0 75 1 5 mm2 Refer to the unit nameplate for rating current Decide the capacity of ELCB or MCCB ELB by below formula Power supply cords of parts of appliances for outdoor use shall not...

Page 14: ...ant local and national regulations Wire size must comply with local and national code For the power cable use the grade of H07RN F or H05RN F materials You should connect the power cable into the powe...

Page 15: ...the head and make proper tightening impossible Over tightening the terminal screws may break them See the table below for tightening torque for the terminal screws Tightening torque N m kgf cm M3 5 0...

Page 16: ...e and position your contraction tube in the middle of the insulation tape Three or more layers of insulation are required Method 1 Method 2 Insulation tape Insulation tape 40 mm 35 mm 6 Apply heat to...

Page 17: ...High Temp button and Low Temp button 3 Check if you have entered the option setting status 4 After entering the option setting status select the option CAUTION Option setting is available from SEG1 t...

Page 18: ...ss the button will be selected in rotation SEG4 SEG5 4 Setting Dry mode Press Mode button to be changed to Dry mode in the ON status 5 Setting SEG6 SEG8 option a Press Low Fan button to enter SEG6 val...

Page 19: ...FF status 11 Setting SEG14 SEG15 option a Press Low Fan button to enter SEG14 value b Press High Fan button to enter SEG15 value Each time you press the button will be selected in rotation SEG14 SEG15...

Page 20: ...de button to be change to Heat mode in the OFF status 19 Setting SEG23 SEG24 mode a Press Low Fan button to enter SEG23 value b Press High Fan button to enter SEG24 value Each time you press the butto...

Page 21: ...ication DetailsI Indication Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 A unit digit 1 Main address setting...

Page 22: ...EG10 SEG11 SEG12 1 EEV Step when heating stops SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 External control External control output External heater On or Off signal S Plasma ion Buzzer Number of hours using...

Page 23: ...SEG9 SEG10 SEG11 SEG12 Explanation PAGE EEV Step when heating stops Indication and Details Indication Details Indication Details Indication Details Indication Details 1 0 Default value 1 Stopped Unit...

Page 24: ...seconds at an interval of 5 minutes in Heat mode 2 1 Fan is turned on continually when the hot water heater is turned on 3 Fan is turned off when the hot water heater is turned on with cooling only in...

Page 25: ...C200 on the outdoor unit and fix it as Cool mode If Fan is set to off for cooling only indoor unit by setting the SEG9 3 or SEG15 3 you need to use an external sensor or wired remote control sensor to...

Page 26: ...when using hot water external heater SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 05 series installation option Detailed Option No 02XXXX 1XXXXX 2XXXXX 3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation...

Page 27: ...30m or 2 Distance2 is 50 110m 6 Use 6sec 5 3 5 5 15 min 7 Use 7sec 6 4 6 7 20 min 8 Use 8sec 7 4 5 30 min 9 Use 9sec A Use 10sec B C D E F Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 Explanation Set t...

Page 28: ...me time as the heating thermostat is on and turned off when the heating thermostat is off e g 2 Setting 02 series SEG15 2 Setting 05 series SEG18 A Room temp set temp f heating compensation temp Exter...

Page 29: ...setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6...

Page 30: ...The appropriate indicator lights up and the air conditioner operates according to the selected mode or function 4 Press the button and check the following The airflow blades work properly Step 15 Prov...

Page 31: ...or on Eva out sensor Short or Open Discharge sensor error Short or Open E122 E123 E126 Indoor fan error E154 Error on outdoor temperature sensor Short or Open Error on cond sensor Error on discharge s...

Page 32: ...ensor is detached Low pressure sensor is detached Outdoor unit copression ration error Outdoor sump down_1 prevetion control Compressor down due to low pressure sensor prevention control_1 Simultaneou...

Reviews: