16
Installation Procedure
English
Instal
lation Pr
oc
edur
e
Outdoor-to-indoor power terminal
specifications
•
Connect the cables to the terminal board using the
compressed ring terminal.
•
Cover a solderless ring terminal and a connector part
of the power cable and then connect it.
Silver solder
Norminal
dimensions
for cable
(mm²)
Norminal
dimensions
for screw
(mm)
B
D
d1
E
F
L
d2
t
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min.
(mm)
Min.
(mm)
Max.
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min.
(mm)
1.5
4
6.6
±0.2
3.4
+0.3
-0.2
1.7
±0.2
4.1
6
16
4.3
+0.2
0
0.7
4
8
2.5
4
6.6
±0.2
4.2
+0.3
-0.2
2.3
±0.2
6
6
17.5
4.3
+0.2
0
0.8
4
8.5
4
4
9.5
±0.2
5.6
+0.3
-0.2
3.4
±0.2
6
5
20
4.3
+ 0.2
0
0.9
•
Connect the rated cables only.
•
Connect using a driver which is able to apply the rated
torque to the screws.
•
If the terminal is loose, fire may occur caused by arc. If
the terminal is connected too firmly, the terminal may
be damaged.
Tightening torque (kgf • cm)
M4
12.0 to 18.0
M5
20.0 to 30.0
•
1N · m = 10 kgf · cm
CAUTION
•
When connecting cables, you can connect the cables to
the electrical part or connect them through the holes
below depending on the spot.
•
Connect the communication cable between the indoor
and outdoor units through a conduit to protect against
external forces, and feed the conduit through the wall
together with refrigerant piping.
•
Remove all burrs at the edge of the knock-out hole
and secure the cable to the outdoor knock-out using
lining and bushing with an electrical insulation such as
rubber and so on.
•
Must keep the cable in a protection tube.
•
Keep distances of 50mm or more between power cable
and communication cable.
•
When the cables are connected through the hole,
remove the Plate bottom.