27
English
Instal
lation Pr
oc
edur
e
Setting the indoor unit addresses manually
1
Turn off the switch 1 of the DIP switches on the outdoor unit HUB PCB, and then turn on the outdoor unit.
2
Manually set the indoor unit options by referring to page 29~34.
3
Press the K3 button once or reset the outdoor unit.
NOTE
•
The LED indications are the same as in the automatic address setting mode.
Setting of PCB Display of the outdoor unit
•
Key option of PCB Display
- K1: Fuction button - K3: Reset button
Key
Push
K1
K3
1
Pipe Checking Operation
Reset
2
Cool Mode Try run
3
Heat Mode Try run
4
Pump Down
5
Finish Key Operation
For more information of the Cool or Heat Try run test, refer to page 35.