ENGLISH-8

Indoor/outdoor unit installation diagram

Maximum 

allowable piping 

elevation 10 m 

or less

6 m or 

less

Install S-trap for 

every 6 m

Maximum allowable 

piping length 20 m 

or less

Outdoor unit

50 cm 

or more

30 cm or 

mor

e

50 cm or 

more

air guide

(Not provided by 

manufacturer )

30 cm or more

20 cm or more

No obstacle 1 m 

or mor

60 cm or mor

e

30 cm 

or more

Protection 

vinyl

Outdoor 

unit leg

Rubber leg

Spare space for piping

•  One S-trap must be installed on the low pressure 

pipe up to 6 m of piping elevation . For piping 
elevation that exceeds 6 m, install S-trap every 
6 m .

CaUtION

Piping length for indoor/outdoor unit installation

 

Refer to illustration on the left for maximum allowable 
piping length and elevation .

 

Since product performance and lifespan may decrease as 
piping length becomes longer, try to minimize the piping 
length but make sure it is over 5 m .

 

Select the installation location where you can keep the 
piping bending to maximum 10 spots .

 

Stated cooling performance is based on product with 5 m 
piping .

Installation space for floor type indoor unit

 

To minimize the waste of space due to  installation, install the indoor unit as 
shown in below figure .

 -

top view

After completing the installation, remove the protection vinyl . 
(Be careful of static electricity) .

After completing the installation, remove the protective 
filament film on the product .

•  Make sure that there are no obstacles (such as curtains etc .) blocking air 

inlets of the indoor unit . 

•  Clear space on the right side of the indoor unit for possible filter 

maintenance in the future .

CaUtION

When air guide needs to be installed to prevent the warm discharge air from 
disturbing the pedestrian, refer to the illustration on the right side for installation .

FAC MEMORY-EU_IM_04036A-03_EN.indd   8

2016-03-30   오전 10:58:21

Summary of Contents for AF**FSSDA Series

Page 1: ...s AF FSZDA Series Air Conditioner installation manual imagine the possibilities ThankyouforpurchasingthisSamsungproduct DB68 04036A 04 EN EL ES FR IT PT DE FAC MEMORY EU_IM_04036A 03_EN indd 25 2016 0...

Page 2: ...11 Installation Drilling a hole and fixing the indoor unit 12 Connecting pipes 12 Connecting drain hose 15 Electrical work 16 Vacuum pump 20 Performing leak test 21 Installing the earth wire 21 Charg...

Page 3: ...outdoor units securely and attach the wires firmly to the terminal block connecting sections so that the pressure is not applied to the sections Inappropriate connection and fixing could cause fire A...

Page 4: ...eck if the product is in good shape before the installation Do not install the product with the damage which occurred during shipment Read the installation manual thoroughly before installing the air...

Page 5: ...when provisions of the installation manual are not complied with the cost required to access and repair the units in SAFETY CONDITIONS as set out in prevailing regulations with harnesses ladders scaff...

Page 6: ...rque wrench 3 Pipe cutter 4 Reamer 5 Pipe bender 6 Spirit level 7 Screw driver 8 Spanner 9 Drill 10 L wrench 11 Measuring tape Tools for test operations 1 Thermometer 2 Resistance meter 3 Electroscope...

Page 7: ...which can bear the weight of the unit A place which can bear the fixing strength of the outdoor unit Avoid a place exposed to oil including machine oil Avoid a saline place Avoid a place exposed to s...

Page 8: ...longer try to minimize the piping length but make sure it is over 5 m Select the installation location where you can keep the piping bending to maximum 10 spots Stated cooling performance is based on...

Page 9: ...r piping 60 cm or more Fixing outdoor unit Follow below method to firmly fix the outdoor unit Using rubber leg Put the rubber leg to the outdoor unit leg Refer to illustration on the right Using ancho...

Page 10: ...n Make sure to check for proper drainage in defrost operation Do not install on the place where bottom part of the outdoor unit is at lower level than the drain hose When installing the drain hose for...

Page 11: ...ries Rubber leg Main power cable Indoor outdoor unit communication cable Indoor Outdoor unit power cable Drain plug Installation accessories Drain connection hose Connection pipe Insulation 6 35 mm Co...

Page 12: ...ing make sure there is no leakage When recovering the refrigerant stop the compressor first before removing the connection pipe If the refrigerant pipe is not properly connected and the compressor wor...

Page 13: ...e of the outdoor unit and tightening by applying appropriate torque Flare process 1 Cut the pipe using the pipe cutter Oblique Rough Burr 90 2 Remove burr on the edge of the pipe If burr is not remove...

Page 14: ...to perform leak test Refer to Performing leak test on pagSe 21 6 Insulate the drain hose after connecting it Insulate it correctly to avoid dew formation Pipe insulation 1 Insulate the refrigerant pi...

Page 15: ...owever if extension is unavoidable due to its short length use silicone sealant to securely seal the connection to prevent leakage Do not use the insulation tape CAUTION Duct drainage Polypropylene PP...

Page 16: ...ure to connect earth wire type Indoor unit Indoor power Indoor outdoor unit power cable Outdoor unit Outdoor power Earth leakage circuit breaker Power 1Ph 220 240V 50 60 Hz Circuit breaker 20 A Indoor...

Page 17: ...d part of the terminal should face upward Installed back to front Compressed part is cut Ring terminal is detached After tightening there should be no gap between a terminal and a screw If there is a...

Page 18: ...s refer to the installation manual CAUTION Unit mm 120 60 20 20 20 180 Power cable provided by us 20 Wire tube power cable 3 Insert both sides of core wire of the power cable into the connection sleev...

Page 19: ...mpleted wrap it with the insulation tape to finish Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of approved reinforced insu...

Page 20: ...r 4 After degree of vacuum has been established open the service valve 1 2 as shown in the illustration Use soapsuds to check for refrigerant leakage on the connection part of the pipes 2 1 F T Conden...

Page 21: ...cted to indoor outdoor units and check the connection part of the indoor outdoor units with soap lather or liquid for leakage test Tightening torque for charging port cap Refer to the table Tightening...

Page 22: ...mation regulation regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Inform users if system contains 5 tCO2e or more of fluorinated...

Page 23: ...outdoor unit over 21 C operate in Cool mode for over 10 minute 6 While pressing and holding the Set Cancel button on the remote controller press the Power button for 3 seconds to display the temperatu...

Page 24: ...FAC MEMORY EU_IM_04036A 03_EN indd 24 2016 03 30 10 58 30...

Reviews: