You can check the drainage only when the air conditioner is
turned on.
N
N
o
o
t
t
e
e
◆
If you do not pour water inside the water supply intake,
water may spill from the indoor unit.
N
N
o
o
t
t
e
e
Testing the drainage
You should test the drainage after completing the installation.
Prepare a little water about 2.0 liter.
Remove two screws on the cover drain pump and pull out the cover.
1
Confirm that the water flows out through the drain hose.
3
Reassemble the cover drain pump and the screws.
4
Pour water into the indoor unit as shown in figure.
2
Cover drain pump
E-
45
ENGLISH
C
C
A
A
U
U
T
T
I
I
O
O
N
N
Do not install air bleeding tubes, as this may
cause water to spray from the drain tube outlet.
Check that the indoor unit is level with the ceiling by using the leveler.
If it is necessary to increase the height of the drain hose
somewhat, the portion directly after 30cm/1ft. If it is raised
higher than 50cm/1 ft , there can be water leaks.
(12")
or less
300
mm
(3~5ft)
1~1.5
m
A
B
C
Do not give the hose and upward gradient after the
connection port. This will cause water to flow backwards
when the unit is stopped, resulting in water leaks.
Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
close to the unit as possible.
1~1.5m(3~5ft)
Upward gradient
Support pieces
1/100 or more
Flexible hose
Band joint
Ceiling
Ceiling
Ceiling
5
8
Unit : mm(ft)
Model
ACC2400C
ACC2800C
ACC4400C
A
200( )
5
8
7
8
258( )
2
7
16
2
7
16
B
550( ) or less 750( )or less
492( ) or less 750(
)or less
1
5
8
1
5
8
C
Air bleeder
Ceiling
ACC2400C IM_E<05381 2002.5.8 1:35 PM Page 45