AA
16
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord .
(Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
Power supply
Communation Cable
Power supply
Max/Min(V)
Indoor Power Cable
1Φ, 220-240V, 50Hz
±10%
2 .5mm²
, 3wires
0 .75~1 .5mm², 2wires
Between Indoor unit and Outdoor unit Connection Cable Specifications(Common in use)
When installing the indoor unit in a computer room or net work room, use the double
shielded (Tape aluminum / polyester braid + copper ) cable of FROHH2R type .
1-phase terminal block spec
AC power : M5 screw
1(L) 2(N)
N
L
15
12
Communication : M3 screw
6 .7
9 .7
Communication : M3 screw
6 .7
9 .7
Communication : M4 screw
10 .1
11 .4
Communication : M4 screw
10 .1
11 .4
3-phase terminal block spec
AC power : M4 screw
N
L3(T)
1(L) 2(N)
L2(S)
L1(R)
9 .95
11 .55
Connecting the cable
3-phase terminal block spec (AC
KXAPNH)
AC power : M6 screw
Communication : M4 screw
L1(R)
L1(S)
L4(N)
L3(T)
28 .0
16 .7
F1
F2
OF2
OF1
R1
R2
8 .0
9 .5
Summary of Contents for AC180JXA NH Series