9
English
Ins
tallation Pr
oc
edur
e
Minimum clearances for the outdoor unit
When installing 1 outdoor unit
(Unit:
mm)
300 or mor
e
1500 or mor
e
300 or
more
600 or
more
300 or
mor
e
2000
or more
1500
or mor
e
600
or mor
e
300
or more
1500
or mor
e
300 or
mor
e
When installing more than 1 outdoor unit
(Unit:
mm)
1500
or more
600
or more
3000
or more
3000
or more
300
or more
600
or more
600
or more
1500
or mor
e
300
or mor
e
1500 or mor
e
600
or more
600
or more
300
or more
600
or more
600
or more
600
or more
300
or mor
e
300 or more
300 or more
500 or mor
e
500 or mor
e
CAUTION
• The outdoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
maintenance, and repair of the unit.
The components of the outdoor unit must be
reachable and removable under safe conditions for
people and the unit.
WARNING
• Should adopt bar type louver. Don’t use a type of rain
resistance louver.
[Bar type louver]
[Rain resistance louver]
• Louver
specifications.
– Angle criteria : less than 20°
– Opening ratio criteria : greater than 80%