7
English
Ins
tallation Pr
oc
edur
e
Installation Procedure
Step 1 Choosing the installation
location
WARNING
• Because your air conditioner contains R-32 refrigerant,
make sure that it is installed, operated, and stored it in
a room whose floor area is larger than the minimum
required floor area specified in the following table:
Minimum required room area (A, m²)
m (kg)
Ceiling-mounted
type
Wall-mounted
type
Floor-standing
type
≤ 1.842
No requirement
1.843
3.64
4.45
28.9
1.9
3.75
4.58
30.7
2.0
3.95
4.83
34.0
2.2
4.34
5.31
41.2
2.4
4.74
5.79
49.0
2.6
5.13
6.39
57.5
2.8
5.53
7.41
66.7
3.0
5.92
8.51
76.6
3.2
6.48
9.68
87.2
3.4
7.32
10.9
98.4
3.6
8.20
12.3
110
3.8
9.14
13.7
123
4.0
10.1
15.1
136
4.2
11.2
16.7
150
4.4
12.3
18.3
165
4.6
13.4
20.0
180
4.8
14.6
21.8
196
5.0
15.8
23.6
213
5.2
17.1
25.6
230
–
m : Total refrigerant charge in the system
–
A :
Minimum required room area
• IMPORTANT: it’s mandatory to consider either the
table 1 or taking into consideration the local law
regarding the minimum living space of the premises.
• Minimum installation height of indoor unit is 0.6 m
for floor mounted, 1.8 m for wall, 2.2 m for ceiling.
Installation location requirements
• Do not place the outdoor unit on its side or upside
down. Failing to do so may cause the compressor
lubrication oil to run into the cooling circuit and lead
to a serious damage to the unit.
• Install the unit in a well-ventilated location away
from direct sunlight or strong winds.
• Install the unit in a location that would not obstruct
any passageways or thoroughfares.
• Install the unit in a location that would not
inconvenience or disturb your neighbors, as they
could be affected by the noise or the airflow coming
from the unit.
• Install the unit in a location where the pipes and the
cables can be easily connected to the indoor unit.
• Install the unit on a flat, stable surface that can
withstand the weight of the unit. Otherwise, the unit
can generate noise and vibration during operation.
• Install the unit so that the air flow is directed towards
the open area.
• Maintain sufficient clearance around the outdoor unit,
especially from a radio, computer, stereo system, etc.
Fuse
Control
1 m or mor
e
1 m or mor
e
1.5 m or more
1.5 m or more
300 mm
Stereo Computer etc
Outdoor Unit
200 mm
Air Guide Duct (This product is not provided by Samsung)
Indoor Unit
• Install the unit at a height where its base can be
firmly fixed in place.
• Make sure that the water dripping from the drain
hose runs away correctly and safely.