24
Installation Procedure
English
Ins
tallation Pr
oc
edur
e
Setting the installation options in a batch
1
Make sure that the power is supplied to the indoor unit. If the indoor unit is not plugged in, it must include a power
supply.
2
The panel(display ) should be connected to an indoor unit to receive option.
3
Set the installation option according to the installation condition of an air conditioner.
– The default setting of an indoor unit installation option is “02000-100000-200000-300000”.
– Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when
there is more than one indoor unit.
– No need to assign SEG3, 6, 9, 10, 11, 16, 21, 22, 23, 24 which are non applicable. Even though those segments
are set, they will be ignored.
– If you set the applicable segments with numbers other than the indiciated, the initial setting will be maintained.
4
Set the indoor unit option by wireless remote controller.
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
RESERVED
Use of external
temperature
sensor
Indoor unit number
RPM setting
compensation
Indication
and details
Indication
Details
Indication
Details
Indication
Details Indication
Details
0. Not used
1. High ceiling mode
2. High ceiling kit
3. Low noise
operation mode
0
A
0
Disuse
0
Disuse
1
Use
1
Use
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
Use of drain pump
RESERVED
RESERVED
RESERVED
Group address
Indication
and details
Indication
Details
Indication
Details
Indication Details
1
0
Disuse
0
slave
1
Use
1
master
2
Use + 3minute
delay