Installation Procedure
Installation Procedure
Step 1 Checking and preparing
accessories
The following accessories are supplied with the indoor
unit. The type and quantity may differ, depending on the
specifications.
User’s manual(1)
Installation manual (1)
Insulation Install Outlet (1)
Insulation Install SVC (1)
Bracket Hanger (1)
Cable-tie (8)
Wireless remote control (1)
Battery (2)
Drain Hose (1)
M4x12 tapped screw(2)
Anti-allergy filter (1)
Deodorizing filter (1)
Remote Control Holder (1)
Step 2 Choosing the installation
location
Installation location requirements
•
There must be no obstacles near the air inlet and
outlet.
•
Install the indoor unit on a ceiling that can support its
weight.
•
Maintain sufficient clearance around the indoor unit.
•
Before installing the indoor unit, be sure to check
whether the chosen location is well-drained.
•
The indoor unit must be installed such that it is
beyond public access and is not touchable by users.
WARNING
•
If appliances contain R-32 refrigerant, then the floor
area of the room in which the appliances are installed,
operated and stored must be larger than the minimum
floor area defined in table below A (m²).
Minimum required room area (A, m²)
m (kg)
Floor-standing type
≤ 1.842
No requirement
1.843
28.9
1.9
30.7
2.0
34.0
2.2
41.2
2.4
49.0
2.6
57.5
2.8
66.7
3.0
76.6
3.2
87.2
3.4
98.4
3.6
110
3.8
123
4.0
136
4.2
150
4.4
165
4.6
180
4.8
196
5.0
213
•
m : Total refrigerant charge in the system
•
A : Minimum required room area