ENGLISH-28
Testing operations
6 .
View Mode : When the K4 switch is pressed, you can see information about our system state as below.
Short
push
Display contents
SEG1
SEG2
SEG3
SEG4
Unit
1
Order frequency
1
Hundreds' digit Tens' digit
Unit digit
Hz
2
Current frequency
2
Hundreds' digit Tens' digit
Unit digit
Hz
3
The number of current indoor units
3
Hundreds' digit Tens' digit
Unit digit
EA
4
The sensor for outdoor air intake
4
+ / -
Tens' digit
Unit digit
°C
5
Discharge sensor
5
Hundreds' digit Tens' digit
Unit digit
°C
6
Eva-Mid sensor
6
+ / -
Tens' digit
Unit digit
°C
7
Cond sensor
7
+ / -
Tens' digit
Unit digit
°C
8
Current
8
Tens' digit
Unit digit
The first place of
decimals
A
9
Fan RPM
9
Thousands'
digit
Hundreds' digit
Tens' digit
rpm
10
Target discharge temperature
A
Hundreds' digit Tens' digit
Unit digit
°C
11
EEV
B
Hundreds' digit Tens' digit
Unit digit
step
12
The capacity sum of indoor units
C
Tens' digit
Unit digit
The first place of
decimals
kW
13
Protective control
D
0: Cooling
1: Heating
Protective control
0: No Protective
control
1: Freezing
2: Non-stop
defrosting
3: Over-load
4: Discharge
5: Total electric
current
Frequency status
0: Normal
1: Hold
2: Down
3: Up_limit
4: Down_limit
-
14
The temperature of heat radiating
plate
E
Hundreds' digit Tens' digit
Unit digit
-
15
S/W check
F
-
-
-
-
Long push 1
Main micom version
Year (Hex)
Month (Hex)
Date (Tens' digit) Date (Unit digit)
After short push 1
Inverter micom version
Year (Hex)
Month (Hex)
Date (Tens' digit) Date (Unit digit)
After short push 1
E2P version
Year (Hex)
Month (Hex)
Date (Tens' digit) Date (Unit digit)
❋
❋
Long push K4(Main micom ver .)
short push 1 more(Inv . micom ver .)
short push 1 more(E2P . ver .)
CAC_Global Duct Latin America_IM_EN_04680A-02.indd 28