Between Indoor unit and Outdoor unit Connection Cable Specifications(Common in use)
Power supply
Communation Cable
Power supply
Max/Min(V)
Indoor Power Cable
1Φ, 220-240 V, 60Hz
±10 %
2 .5 mm
²
, 3wires
0 .75~1 .5 mm², 2wires
X
f
Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord . (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
When installing the indoor unit in a computer room or net work room, use
the double shielded (Tape aluminum / polyester braid + copper ) cable of
FROHH2R type .
1-phase terminal block spec
AC power : M5 screw
Communication : M4 screw
Communication : M3 screw
1(L) 2(N)
N
L
15
12
10 .1
11 .4
6 .7
9 .7
3-phase terminal block spec
AC power : M4 screw
Communication : M4 screw Communication : M3 screw
N
L3(T)
1(L) 2(N)
L2(S)
L1(R)
9 .95
11 .55
10 .1
11 .4
6 .7
9 .7