Install the power cable and communication cable of the indoor and
outdoor unit at least 1 m (3.26’) away from the electric appliance.
Install the indoor unit away from lighting apparatus with a ballast.
X
X
If you use the wireless remote control, reception error may occur due
to the ballast of the lighting apparatus.
For maximum safety, installers should always carefully read the
following warnings.
Do not install the air conditioner in following places:
X
X
Place where there is mineral oil or arsenic acid.
Plastic parts may deform,crack resulting water leak and reduce
performance of heat exchanger or air conditioner may not operate.
X
X
The place where corrosive gas such as sulfurous acid gas generates
from vent pipes or other outlets.
X
X
The copper pipe or connection pipe may corrode and refrigerant
may leak.
X
X
A place where there is a machine that generates electromagnetic
waves. The air conditioner may not operate normally due to control
system interference.
X
X
The place where there is a danger of existing combustible gas,
carbon fiber of flammable dust.
X
X
The place where thinners or gasoline are handled. Gas may leak and
it may cause fire.
If the air conditioner is installed in a small room, measures must
be taken to prevent the refrigerant concentration in the room
from exceeding the safety limit in the event of refrigerant leakage.
Consult a dealer regarding the appropriate measures to prevent the
allowable concentration from being exceeded.
X
X
If the refrigerant leaks, and cause the concentration limit to be
exceeded, hazards due to lack of oxygen in the room may result.