Annex
CO/PA
Function/
designation
Setting/
adjustment range
Control function
M1
Control mode
0: Fixed set point/follow-up
1: Override (MIN selection)
2: Override (MAX selection)
3:
Controller [1] active when LIM1 = off / Control
-
ler [2] active when LIM1 = on
4:
Controller [1] active when LIM2 = off / Control
-
ler [2] active when LIM2 = on
5:
Controller [1] active when DI1 = off / Controller
[2] active when DI1 = on
6:
Controller [1] active when DI2 = off / Controller
[2] active when DI2 = on
7:
Controller [1] active when DI3 = off / Controller
[2] active when DI3 = on
8:
Controller [1] active when DI4 = off / Controller [2]
active when DI4 = on
9: Cascade
M2
Direction of action
0:
>> (increasing/increasing)
1:
<> (increasing/decreasing)
Internal limit LIM1/Internal limit LIM2
LIM1.S/
LIM2.S
Source
1: Measured value AI1
2: Measured value AI1 after function generation
3: Measured value AI2
4: Measured value AI2 after function generation
5: Measured value AI3
6: Measured value AI3 after function generation
7: Measured value AI4
8: Measured value AI4 after function generation
9:
Actual value [1] before comparator
10:
Set point [1] before comparator
11:
Set point deviation [1] before comparator
12:
Actual value [2] before comparator
13:
Set point [2] before comparator
14:
Set point deviation [2] before comparator