1.3
Displaying data
The states of the inputs and outputs as well as information on the connected meter bus instru-
ments can be retrieved in the information level. In addition, the analog and binary outputs can
be changed (refer to section 3 on manual operation).
The information level is divided into individual menu items:
4
Analog inputs
· Measured data from connected sensors
4
Analog outputs
· Output data from four analog outputs *
)
4
Binary inputs
· States of the binary sensors (on/off)
4
Binary outputs
· States of the binary outputs (on/off) *
)
4
Meter bus
· Output data of the meters connected over meter bus
*
)
The analog and binary output settings can be changed after entering the key code.
Proceed as follows:
Switch to the information level.
Display: Information level
The menu item “Analog inputs“ is highlighted.
Select required menu item, e.g. binary outputs.
Activate the menu item.
Select required data point.
Returning to the information level
Select
Back to return to the information level.
Exit the menu item.
Display: Information level
Exiting the information level
Select
Back.
Exit the information level.
Display: Normal display (depending on the
application)
Note!
If no key is pressed for two minutes, the PLC automatically returns to the normal display.
EB 5571 EN
7
Operation
Information level
Analog inputs
Analog outputs
Binary inputs
Binary outputs
Meter bus
System info
Back
Information level
Analog inputs
Analog outputs
Binary inputs
Binary outputs
Meter bus
System info
Back
Binary outputs
BA07=OFF
BA08=OFF
BA09=OFF
BA10=OFF
BA11=OFF
BA12=OFF
Back