Function block parameters (CO1 and CO2)
Level 1
Level 2
Range of values
Limiting factor (F03 - 1)
0.1 to 10.0
Temperature rise (F05 - 1)
1 to 10 °C/24 h
Maximum temperature (F05 - 1)
25 to 60 °C
Maintaining time of max. temp. (F05 - 1)
1 to 10 days
Temperature reduction (F05 - 1)
0 to 10 °C/24 h
Cycle time (F09 - 1)
1 to 100 min
Proportional gain K
P
(F12 - 1)
0.1 to 50
Reset time T
N
(F12 - 1)
1 to 999 sec
Derivative-action time T
V
(F12 - 1)
0 to 999 sec
Transit time T
Y
(F12 -1)
15 to 240 sec
Hysteresis (F12 - 0)
1 to 30 °C
Min. ON time (F12 - 0)
0 to 10 min
Min. OFF time (F12 - 0)
0 to 10 min
Max. deviation (F13 - 1)
2 to 10 °C
EB 5576 EN
135
Appendix