12.2 Parameter lists
PA1 (
): Parameter level Heating circuit RK1
PA2 (
): Parameter level Heating circuit RK2
Display
Parameter designation
Range of values (default)
Gradient, flow
0.2 to 3.2 (1.8)
(with CO1, 2 -> F05 - 1: 0.2 to 1.0 (1.0) applies)
Level (parallel shift)
–30 to 30 °C (0 °C)
Min. flow temperature
5 to 130 °C (20 °C)
Max. flow temperature
5 to 130 °C (90 °C)
(with CO1, 2 -> F05 - 1: 5 to 50 °C (50 °C) applies)