F Function
WE
Anl
Comment
Function block parameters
/ Range of values (default)
03 TROVIS 5570
Room Panel in RK1
0
1.0–1.4,
2.x, 4.x,
10.x, 11.x
CO7 -> F03 - 1: Communication with TROVIS 5570 active
for RK1; CO1 -> F01 - 1 is set automatically
Function block parameter:
Device bus address / Auto*, 1 to 32 (32)
*Auto = controller automatically searches for a room panel
for which detection mode has been activated
04 TROVIS 5570
Room Panel in RK2
0
3.x, 4.x,
10.x
CO7 -> F04 - 1: Communication with TROVIS 5570 active
for RK2; CO2 -> F01 - 1 is set automatically
Function block parameter:
Device bus address / Auto*, 1 to 32 (32)
*Auto = controller automatically searches for a room panel
for which detection mode has been activated
05 Reserved
06 Send value AF1
0
All
CO7 -> F06 - 1:
Function block parameter:
Register no. / 1 to 4 (1)
07 Receive value AF1
0
All
CO7 -> F07 - 1:
Function block parameter:
Register no. / 1 to 4 (1)
08 Send value AF2
0
All
CO7 -> F08 - 1:
Function block parameter:
Register no. / 1 to 4 (2)
09 Receive value AF2
0
All
CO7 -> F09 - 1:
Function block parameter:
Register no. / 1 to 4 (2)
10 Send flow set point
RK1
0
All
CO7 -> F10 - 1: In systems Anl 1.5–1.8, 2.x, 3.1–3.4,
4.1–4.3, 7.x, 8.x, the storage tank charging set point is sent
during DHW heating
Function block parameter:
Register no. / 5 to 64 (5)
11 Send flow set point
RK2
0
All
CO7 -> F11 - 1:
Function block parameter:
Register no. / 5 to 64 (5)
12 Reserved
13 Send flow set point
DHW
0
All
CO7 -> F13 - 1: In level PA4, the
Charging temperature
boost
parameter is generated
Function block parameter:
Register no. / 5 to 64 (5)
EB 5576 EN
117
Appendix