12.6 Customer data
Station
Operator
Responsible Samson office
System code number
Function block settings
Fb
ON/ OFF
Options selected, function block parameters
1
2
3
4
5
6
7
Mixed air temperature control
Operation in sequence with extract air temperature;
Operation in sequence with exhaust air temperature
Outdoor temperature-compensated mixed air chamber operation
8
9
10
Enable night purge (START): [24] °C
Finish night purge (STOP): [18] °C
Temperature difference to outdoor temperature: [5] °C
11
Speed 2: BA2 = BA3 = ON or BA2 = OFF, BA3 = ON
Delay time: [0] sec
12
OFF
Enable chiller at outdoor temperature (START): [18] °C
ON
SEQ
Activating value (START): [30] %;
Deactivating value (STOP): [10] %
PAr
Minimum deactivation time (STOP MIN): [600] sec;
Minimum activation time (START MIN): [600] sec;
Cooling deactivated when Y1 > (STOP): [50] %
13
EB 5477 EN
111
Appendix