24
EB 7500 EN
Installation
Fig. 14:
Installation dimensions of panel-mounted devices and Type 3426-2 Control Room Housing
137,5
144
25
320/180
72
100
90
80
70
60
30
20
10
40
0
ca.157
51
1)
44
124
17,3
86
22
Ø4,5
Ø4,5
13,5
77,5
55
R
w
Z
y
A
S
x
9,5
21
21
21
21
21
6 Installation
Panel-mounted devices (Type 3421,
Type 3422, Type 3427, Type 3416, and
Type 3417)
All devices have the front dimensions
72 x 144 mm and require a control panel
cut-out of 138
+1
x 68
+0.7
mm.
The devices are fastened at the top and bot-
tom to a rail (Type 3421/3422: 1089-0036
and Type 3427: 1089-0037) in the control
panel.
The tightening torque for the screws depends
on the installation situation (approx.
1.4 Nm). On tightening the screws, the rail
must have direct contact with the housing
and the panel must not be bent.
Pneumatic
connections
Electrical
connections
Terminal rail
All dimensions in mm
Approx. 135 mm with Type 3423...,
approx. 170 mm with
Type 3423... + Type 3424
Control room housing
Devices for panel mounting
Mid distance
between devices:
min. 73 mm
horizontally and
170 mm
vertically.
u
T 7506,
u
T 7526,
u
T 7527.
Terminal rail
Type 3424
1)
180 mm: Types 3427, 3416-1.../-90, 3417-1...
320 mm: Types 3421, 3422, 3416-2.../-91, 3417-2...