EB 7500 EN
33
Conversion
9.2 Operating mode change-
over in Type 3424-2 i/p
Converter
The i/p module is in the x input in x mode
and in the w
ext
input in w
ext
mode.
1. Release lock and completely pull out the
plug-in unit.
2. Pull the three-pin cable connector for the
mA signal off the converter board.
3. Unscrew the fastening screw (6) at the
controller module and pull the module off
together with the i/p converter from the
self-seal push-on fittings. Lift it out of the
control station.
4. Pull the three-pin cable connector for the
mA signal off the terminal plate.
5. Swap the location of the O-ring and
washer on the holes on the inside of the
plate as shown in Fig. 20.
x mode
6. Seal tight the w
ext
input of the compact
controller connecting plate (Fig. 16) with
a screw plug with
1
/
8
NPT thread.
The w
ext
port at the plug connection of
the control station must be sealed.
w
ext
mode
7. Open the w
ext
port at the plug connection
by unscrewing the M4 hexagon socket
screw at the w
ext
port and insert 4 x 2
O-ring included.
Seal tight the w
ext
input of the compact
controller connecting plate (Fig. 16) with
the
1
/
8
NPT screw.
8. Reinstall converter and plug on the cable
connector.
Fig. 20:
Operating mode changeover of i/p
converter
5
6
Self-seal push-on
fittings
Blanking
plug w
ext
Washer for x mode
O-ring for w
ext
mode
O-ring for w
ext
mode
Washer for x mode