![Samson EB 31a-23 Mounting And Operating Instructions Download Page 25](http://html1.mh-extra.com/html/samson/eb-31a-23/eb-31a-23_mounting-and-operating-instructions_4031618025.webp)
8-1
EB 31a-23_EN
Edition: November 2021
Speci
fi
cations subject to change
Malfunctions
8 Malfunctions
The work described in this section is only to be performed by fully trained and quali
fi
ed personnel.
8.1 Troubleshooting
Malfunction
Possible reasons
Recommended action
Uneven rotation
Inadequate supply
Check the supply system and make sure that the supply pressure is correct.
Missing lubricant
Disassemble the actuator, lubricate all the sliding parts and reassemble the ac-
tuator.
Worn components
Disassemble the actuator, inspect and replace the worn/damaged compo-
nents.
Control system
Make sure the control system components are correctly assembled. Check the
control system documentation and contact the manufacturer.
Faulty valve
In case of actuator mounted over the valve, check the valve documentation
and contact the manufacturer.
Incomplete rotation
Incorrect stroke adjustment
Follow the indications in section 9.5.8 for correct stroke adjustment.
Foreign object left inside
Disassemble the actuator, inspect and remove any foreign object.
Incorrect assembly after maintenance
Disassemble and reassemble the actuator correctly.
Hydraulic circuit blocked, compressed or
with speed control valve problems
Check all the tubing and
fi
ttings, remove any foreign object/damaged compo-
nent.
Control system
Make sure the control system components are correctly assembled. Check the
control system documentation and contact the manufacturer.
Faulty valve
In case of actuator mounted over the valve, check the valve documentation
and contact the manufacturer.
Loss of power
Inadequate supply pressure
Check the control system and make sure that the supply pressure is correct.
Supply pipe blocked, compressed or with
sealing problems
Check all the tubing and
fi
ttings, remove any foreign object/damaged compo-
nent.
Actuator seals leakage
Disassemble the actuator, inspect and replace any damaged seals.
blocked air exhaust hole
Remove plugs or foreign objects from the exhaust hole.
Faulty valve
In case of actuator mounted over the valve, check the valve documentation
and contact the manufacturer.
Uneven deceleration
Missing hydraulic oil
Make sure the HCD chambers bodies are correctly
fi
lled.
−
Contact PFEIFFER after-sales service for malfunctions not listed
in the table.
−
Spare parts are to be ordered with all information acc. to the
identi
fi
cation of the actuator. Only original parts from PFEIFFER
Chemie-Armaturenbau GmbH may be installed.
8.2 Emergency
action
The plant operator is responsible for emergency action to be tak-
en in the plant.
Note
Summary of Contents for EB 31a-23
Page 20: ...5 4 EB 31a 23_EN Edition November 2021 Specifications subject to change Mounting and assembly...
Page 22: ...6 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Start up...
Page 24: ...7 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Operation...
Page 26: ...8 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Malfunctions...
Page 42: ...9 16 EB 31a 23_EN Edition November 2021 Specifications subject to change Service...
Page 44: ...10 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Decomissioning...
Page 48: ...12 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Repairs...
Page 50: ...13 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Disposal...
Page 52: ...14 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Certificate...
Page 53: ...14 3 EB 31a 23_EN Edition November 2021 Specifications subject to change Certificate...
Page 54: ...14 4 EB 31a 23_EN Edition November 2021 Specifications subject to change Certificate...
Page 61: ...EB 31a 23_EN Edition November 2021 Specifications subject to change...
Page 62: ...EB 31a 23_EN Edition November 2021 Specifications subject to change...
Page 63: ...EB 31a 23_EN Edition November 2021 Specifications subject to change...