Mounting and assembly
Before mounting the actuator over the valve, make sure the fol-
lowing conditions are met:
−
The actuator is not damaged.
−
The type designation, material and temperature range of the
actuator match the ambient conditions (temperatures etc.).Re-
fer to section “2 Markings on the device” for name plate de-
tails.
−
Check compatibility of the valve stem to the actuator bore.
The length, size and con
fi
gurations must match.
−
Check compatibility of actuator, valve and bracket bolting
pattern.
−
Before
fi
tting the actuator over the valve, make sure that the
actuator and the valve are correctly oriented, with reference
to the rotation direction and fail action required.
−
Make sure that the tubing,
fi
ttings and seals connected to the
actuator are cleaned to prevent foreign matter/objects enter-
ing into the actuator’s chambers.
−
When
fi
tting accessories over the actuators, assemble them in
such a way that the emergency controls are easily accessible
for emergency manual operation.
−
Check that the exhaust ports are not obstructed.
−
Remove the plugs from the actuator air connections during
installation and operation, protect and close the air connec-
tions which may not being used immediately.
−
Make sure that the operating pressure media composition
used for the actuator operation meets the operating condi-
tions given in this manual and corresponds to what the actu-
ator was manufactured for. Refer to section “3 Design and
principle of operation”.
−
It is the user responsibility to ensure that actuator and control
components must be protected from electrical spikes, surge
and lightning strikes as well as all magnetic
fi
elds.
−
Prevent any dangerous and/or corrosive substances in the
working environment enter into the internal chambers by us-
ing adequate
fi
lters and/or solenoid valves and/or any other
appropriate system.
Fig.
|
5-2:
Mounting the valve
Refer to Fig. 5-2 and proceed as follows to mount the actuator
over the valve:
Ö
Disconnect any electrical/pneumatic/hydraulic power supply
Ö
Lay out the necessary material and tools to have them ready
during mounting
Ö
The actuator is supplied in the fail position (for single-acting),
so drive the valve in the right position as per the actuator fail
position
Ö
Clean the actuator‘s bore and the bottom
fl
ange
Ö
Clean the valve and the actuator interface to remove com-
pletely any lubricant
Ö
Place the bracket, if any, over the valve
fl
ange, tighten all
bolts and nuts and apply the correct tightening torque
Ö
Assemble the coupling at
fi
rst into the valve stem before the
assembly of the actuator
Ö
Lift the actuator
Summary of Contents for EB 31a-23
Page 20: ...5 4 EB 31a 23_EN Edition November 2021 Specifications subject to change Mounting and assembly...
Page 22: ...6 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Start up...
Page 24: ...7 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Operation...
Page 26: ...8 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Malfunctions...
Page 42: ...9 16 EB 31a 23_EN Edition November 2021 Specifications subject to change Service...
Page 44: ...10 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Decomissioning...
Page 48: ...12 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Repairs...
Page 50: ...13 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Disposal...
Page 52: ...14 2 EB 31a 23_EN Edition November 2021 Specifications subject to change Certificate...
Page 53: ...14 3 EB 31a 23_EN Edition November 2021 Specifications subject to change Certificate...